Description
Value or Value range/ Default
Name
Data type: Integer
Access: No limitations
Makes it possible for clients to reset the
OPC server. A reset means that the server
disconnects all clients and reloads the
configuration file.
When the last client is discon-
nected the server usually shuts
down. The server does not shut
down if it was not started by the
COM runtime or if it is running
as a Windows service. In that
case the configuration file is not
reloaded.
By writing 1 the server is reset.
By writing 2 the log file is
cleared.
Other values are currently
ignored.
Reset
Data type: Text
Access: Read-only
The file version number of the OPC
server/client exe file.
Version information
File version
Data type: Text
Access: Read-only
The version (revision) of the package that
the server/client belong to.
Version information
Product version
Timesync client
Data type: Integer
Access: No limitations
Status of the integrated SNTP clients time
synchronization routine. Value is 0 when
not in use and 1 when in use. By writing
0 the client is started and by writing 1 it is
stopped. The client can be started only if
configuration parameters are given in a
configuration file.
0 = Not in use
1 = In use
Default: 1
In use
Data type: Boolean
Access: Read-only
Status of the integrated SNTP client time
synchronization routine. Value is false
when synchronization is not received and
true when synchronization received and
local time set OK.
False = Not synchronised
True = Synchronised OK
Timesync status
Timesync server
62
1MRS758690
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual