Protection activation information (ACT)
4.2.6.
ACT represents DMCD M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, M_DP_NA_1,
M_DP_TA_1, M_DP_TB_1.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/ Value
range
Type
Name
VT_BOOL
SPI
M
BOOLEAN
general
VT_BOOL
SPI
O
BOOLEAN
phsA
VT_BOOL
SPI
O
BOOLEAN
phsB
VT_BOOL
SPI
O
BOOLEAN
phsC
VT_BOOL
SPI
O
BOOLEAN
neut
VT_I4
EI, BL, SB, NT, IV
M
Quality
q
Directional protection activation information (ACD)
4.2.7.
ACD represents M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, M_DP_NA_1, M_DP_TA_1,
M_DP_TB_1.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/ Value
range
Type
Name
VT_BOOL
SPI
M
BOOLEAN
general
VT_I4
M
unknown
forward
backward
ENUMERATED
dirGeneral
VT_BOOL
SPI
O
BOOLEAN
phsA
VT_I4
O
unknown
forward
backward
ENUMERATED
dirPhsA
VT_BOOL
SPI
O
BOOLEAN
phsB
VT_I4
O
unknown
forward
backward
ENUMERATED
dirPhsB
VT_BOOL
SPI
O
BOOLEAN
phsC
VT_I4
O
unknown
forward
backward
ENUMERATED
dirPhsC
VT_BOOL
SPI
O
BOOLEAN
neut
91