Supported transmission modes:
•
Modbus RTU
•
Modbus ASCII
Table 2.4.4-1 The function codes supported by Modbus OPC Server
Memory area
Description
Function code
00001 - 09999
Read coil status
01
10001 - 19999
Read input status
02
40001 - 49999
Read holding register
03
30001 - 39999
Read input registers
04
00001 - 09999
Force single coil
05
40001 - 49999
Write single register
06
40001 - 49999
Write multiple registers
16
60001 - 65535
Write General Reference
21
The following data formats are supported:
•
Bit, one coil, or input status
•
Word, one register in IED's memory. The data is used in an unsigned form
•
Integer, one register in IED's memory. The MSB bit is used as a sign bit
•
Long MSW last, signed 32-bit object, which needs two registers from IED's memory
in lsw-msw order
•
Long MSW first, signed 32-bit object which needs two registers from IED's memory
in msw-lsw order.
•
Float MSW last, floating point type which needs two input registers from IED's
memory in lsw-msw order
•
Float MSW first, floating point type which needs two input registers from IED's
memory in msw-lsw order.
External OPC Server features
2.4.5.
OPC Data Access is used for continuous, real-time data communication between
PLC/DCS systems and COM600 communicating real-time data from data acquisition
devices such as PLCs to display and interface devices like Web Human-Machine Inter-
faces (WebHMI). OPC DA is also used for inter-process communication in COM600.
SNMP features
2.4.6.
The Simple Network Management Protocol (SNMP) is used to manage network con-
nectivity of substation devices in the substation LAN network.
The SNMP OPC Server is intended for providing methods for OPC clients to monitor
network-attached devices.