CBV-2U4-3T(-N) Control Sequences
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
41
M
AN0
13
9
re
v
14
VAV Modulating HW Reheat with variable speed fan Tri-state
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button)
UI-02
Setpoint Adjustment (optional 5K slider)
UI-03
Discharge Temperature (optional)
UI-04
CO
2
, Humidity, or occupancy signal (all optional)
UI-08
Flowrate Sensor
DO-09
Damper Control (CBV-2U4-3T-N only)
DO-10
Damper Control (CBV-2U4-3T-N only)
DO-11
Heat Valve Open
DO-12
Heat Valve Close
DO-13
AO-14
AO-15
Variable Speed Parallel or Series Fan Speed Command (0
…
10 Vdc)
AO-16
Damper Control (CBV-2U4-3T only)