CBV-2U4-3T(-N) |
Control Sequence Overview
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
45
M
AN0
13
9
re
v
14
STANDBY STATE OF OPERATION
After the warm-up state is complete, the master controller may (optionally) set the terminal unit to the standby
state. This state may be utilized to maintain a zone ready for occupancy with minimum energy utilization.
When in the standby state, the occupied temperature setpoints will be used. When the unit is in a deadband
mode, the primary air damper will be closed, or controlled to a reduced Flowrate setpoint.
Variable speed series and parallel fan powered terminal units will be controlled to the
(A227) setpoint when there is no heating or cooling demand.
•
Included in the GroupXOccCode command R/W
•
PRIMARY AIR MODE
Primary Air Mode is either
ON
or
OFF
. Typically, the master controller writes this command to the
CBV-2U4-3T(-
N)
box based on AHU fan status or similar start/stop logic. By default, the Primary Air Mode is OFF, and the
CBV-2U4-3T(-N)
will allow the damper to operate in unoccupied mode.
•
Included in the GroupXOccCode command R/W
•
(D122) RO
LOAD SHED ENABLE
If the master controller commands load shed on to this
CBV-2U4-3T(-N)
or the group it is a member of, the
effective cooling setpoint will be shifted up, and the effective heating setpoint shifted down, by
LoadShedOccStptOffset
(A198).
•
Included in the GroupXOccCode command R/W
•
(A198) R/W
•
(A66) RO
FIRE STOP COMMAND
The fire stop command will close the primary air damper and de-energize all fans and stages of heat.
•
Included in the GroupXOccCode command R/W
•