CBV-2U4-3T(-N) |
Appendix : List of CBV-2U4-3T(-N) points
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
62
M
AN0
13
9
re
v
14
ANALOG VALUES
POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
UNITS AND DEFAULT VALUES
IMPERIAL STG.
METRIC STG.
1
yes
RemoteSlaveDehumidCmd (A1)
Remote dehumidification command
setpoint
0
…
100 %
0
%
0
%
2
yes
OfflineTimerCommTestValueBACnet
(A2)
Required to write a 1 to this point
every 5
…
10 minutes when offline
timer for BACnet communications
point
is enabled.
1
no-units
1
no-units
3
yes
ElecHeatCFMTestStpt (A3)
Minimum Flowrate setpoint to enable
electric heat. Applicable only for VAV
boxes configured for no fan or series
fan.
0
cfm
0
l/sec
7
Yes
CFMAbvBlwSPAlarm (A7)
Flowrate error from current
calculated Flowrate setpoint alarm
75
cfm
37.5
l/sec
10
No
UI04ScaledValueCO2 (A10)
Scaled value from local CO
2
sensor
0
ppm
0
ppm
12
No
UI04ScaledValue (A12)
Scaled value from local relative
humidity sensor
0
%RH
0
%RH
13
No
ZoneRHValueCV (A13)
Local relative humidity reading from
sensor
0
%RH
0
%RH
19
Yes
StuckDamperDB (A19)
CBV-2U4-3T ONLY
The percentage difference between
requested and actual Damper %
where the damper will be considered
close enough (Damper Requested
–
Deadband) > Damper Actual >
(Damper Req Deadband)
20
%
20
%
20
Yes
StuckDamperDelay (A20)
CBV-2U4-3T ONLY
The minimum amount of time in
seconds before an alarm is raise for a
stuck damper
60
sec
60
sec
22
No
AFS_PressurePa (A22)
Pressure Reading
0
pascals
0
pascals
24
No
Damper Feedback (A24)
Feedback Position of Damper
actuator (CBV-2U4-3T ONLY)
%
%
28
No
AFS_PressureIn (A28)
Pressure Reading
0
inH
2
0
Imperial
Only
Imperial
Only
32
Yes
HeatingOffsetPID (A32)
Offsets effective heating setpoint at
PID
0
°F
0
°c
39
Yes
CoolingOffsetPID (A39)
Offsets effective cooling setpoint at
PID
0
°F
0
°c
40
No
Fusion_ZoneTemp (A40) without
Actuator
The space temperature as detected
by the FusionAir sensor. (FA Variants
only)
0
°F
0
°C
41
No
AlarmEncode (A41)
Encodes various alarms as follows:
0=No Alarm
1=Low Temp Alarm
2=High Temp Alarm
4=Low Air Flow
8=High Air Flow
16=Local Temp Fault
32= No MSTP comms to master
0
no-units
0
no-units
47
Yes
AO15RemoteCmd (A47)
Remote command for AO15
0
%
0
%
62
No
Fusion_ZoneHumidity(A62) without
Actuator
The space humidity as detected by
the FusionAir sensor. (FA Variants
only)
0
%rh
0
%rh
66
No
EffLoadShedOccStptOffset (A66)
Effective load shed occupied setpoint
offset
0
°F
0
°C
67
No
ZoneCO2ValueCV (A67)
Local CO
2
reading from sensor
0
ppm
0
ppm
71
No
HiSelectCO2DehumidEffAFlowCmd
(A71)
Maximum of CO
2
or dehumidification
effective airflow setpoint
0
no-units
0
no-units
75
Yes
RemoteSlaveCO2Cmd (A75)
Remote CO
2
command setpoint
0
…
100%
0
%
0
%
76
No
LocalRemoteSlaveC02Calc (A76)
Current CO
2
command 0
…
100%
0
%
0
%
77
Yes
Group0TABCode (A77)
Group 0 TAB code
0
no-units
0
no-units