Wiring the Digital and Analog Outputs
Both
CBV-2U4-3T
and
CBV-2U4-3T-N
come with 3 digital outputs and 2
UniPuts™
(normally configured as
analog outputs) for controlling a wide variety of possible elements of the VAV box. In addition the
CBV-2U4-
3T-N
comes with 2 digital outputs for damper control (accessed by removing the top cover), and the
CBV-
2U4-3T
includes integrated damper control. It is possible to control single speed and variable speed fans
(both parallel and series), electric heat (optional pulse width modulation), proportional heating valves, and
tri-state heating valves depending on the application.
•
DO-11
can be configured for controlling first stage electric heat (on-off or pulse width modulation
optional), or to open a tri-state heating valve.
•
DO-12
can be configured for controlling second stage electric heat (on-off or pulse width modulation
optional), or to close a tri-state heating valve.
•
DO-13
can be configured for controlling third stage (on-off or pulse width modulation optional), or to
control a single speed fan (series or parallel).
Note:
It is also possible to define
DO-13
as a start command for a variable speed fan (series or parallel).
Both
AO-15
and
DO-13
must be configured as either series or parallel for this feature.
•
AO-14
can be configured for controlling any first stage modulating heating valves,
SCR
(
Silicone
Controlled Rectifier
), or E
MC
(
Electronic Modulating Control
) type controls depending on the heating
elements of the VAV box.
•
AO-15
can be configured for controlling any second stage modulating heating valves, SCR (
Silicone
Controlled Rectifier
), or
EMC
(
Electronic Modulating Control
) type controls depending on the heating
elements of the VAV box. This output can also be configured for variable speed fan control (series or
parallel).
Note:
AO-14
and
AO-15
are preconfigured as a 0
…
10 V dc direct acting output. During configuration it is
possible to configure either output or both outputs for reverse acting or 10
…
0 V dc. Either or both
of these outputs can also be configured for 2
…
10 V dc
or 10
…
2 V dc. In
CBV-2U4-3T-N
controllers
the
DO
s can now be configured for reverse acting.
IO POINTS
DESCRIPTION
DO-09
Damper Open/Close CBV-2U4-3T-N ONLY
DO-10
Damper Close/Open CBV-2U4-3T-N ONLY
DO-11
1
st
Stage Electric Heat (optional PWM) or Tri-State Heat Valve Open
DO-12
2
nd
Stage Electric Heat (optional PWM) or Tri-State Heat Valve Closed
DO-13
3
rd
Stage Electric Heat (optional PWM) or Fan Command (Series or Parallel)
AO-14
1
st
Stage Modulating Heat Control
AO-15
2
nd
Stage Modulating Heat Control or Variable Fan Speed Control (Series or
Parallel)