Zeroing Airflow sensor
The
CBV-2U4-3T(-N)
comes from the factory with the airflow sensor zeroed. To compensate for possible air
leakage around the damper, users are able to zero the airflow sensor in the field. To zero the airflow sensor,
users will need to do the following:
1.
Drive damper to the closed position by enabling
(D192).
2.
After damper has fully shut, set
After 10 seconds the
(D150) will be automatically set back to off and the airflow sensor will
now be zeroed. Be sure to disable
(D192) when finished with this step.
Airflow Calibration Procedure
1.
Airflow sensor calibration sensor using
flow selection in the firmware block
VAV
flow calculation.
1.1 Set Max cfm flow at
1.2 Set to
to
TRUE
.
1.3 Set
to
TRUE
.
1.4 Allow airflow
1.5 Enter balancers airflow reading in CFM in
1.6 Again, allow airflow
to reach
1.7 Repeat as necessary.
1.8 Calculated K factor can be read at
1.9 Set
FALSE
when complete.
2.
Airflow sensor calibration sensor using the
K-
factor selection in firmware block VAV flow calculation
.
2.1 Set
to
FALSE
.
2.2 Set
to the K-factor specified by the unit manufacturer.
2.3 Calculated flow can be read at
Note
: If
is
TRUE
and balancing is finished, toggling
to
FALSE
will cause the
K Factor
, and
will be
set back to
FALSE
. It is recommended to save final
K Factor
to
FALSE
after balancing. This will ensure the
K Factor
is not lost on a firmware upgrade.