2)
For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
This table shows the requirements when a non-ABB motor is in use.
Requirement for
Nominal AC supply
voltage
Motor
type
ABB du/dt and common mode filters, insulated N-end
motor bearings
Motor insula-
tion system
P
N
≥ 350 kW
or
frame size ≥ IEC 400
100 kW ≤ P
N
< 350
kW
or
IEC 315 ≤ frame size
< IEC 400
P
N
< 100 kW
and frame
size <
IEC 315
P
N
≥ 469 hp
or
frame size >
NEMA 580
134 hp ≤ P
N
< 469 hp
or
NEMA 500 ≤ frame
size ≤ NEMA 580
P
N
< 134 hp
and frame
size <
NEMA 500
+ N + CMF
+ N or CMF
-
Standard:
Û
LL
= 1300 V
U
N
≤ 420 V
Random-
wound
and form-
wound
+ N + d
u
/d
t
+ CMF
+ d
u
/d
t
+ (N or CMF)
+ d
u
/d
t
Standard:
Û
LL
= 1300 V
420 V <
U
N
≤ 500 V
or
+ N + CMF
+ N or CMF
-
Reinforced:
Û
LL
= 1600 V,
0.2 micro-
second rise
time
+ N + d
u
/d
t
+ CMF
+ d
u
/d
t
+ (N or CMF)
+ d
u
/d
t
Reinforced:
Û
LL
= 1600 V
500 V <
U
N
≤ 600 V
or
+ N + CMF
+ N or CMF
-
Reinforced:
Û
LL
= 1800 V
+ N + d
u
/d
t
+ CMF
+ d
u
/d
t
+ N
+ d
u
/d
t
Reinforced:
Û
LL
= 1800 V
600 V <
U
N
≤ 690 V
+ N + CMF
+ N + CMF
-
Reinforced:
Û
LL
= 2000 V,
0.3 micro-
second rise
time
1)
1)
If the intermediate DC circuit voltage of the drive is increased from the nominal level due to long term resistor
braking cycles, check with the motor manufacturer if additional output filters are needed in the applied drive
operation range.
The abbreviations used in the tables are defined below.
Definition
Abbr.
Nominal AC line voltage
U
N
Peak line-to-line voltage at motor terminals which the motor insulation must withstand
Û
LL
Motor nominal power
P
N
d
u
/d
t
filter at the output of the drive
d
u
/d
t
Common mode filter
CMF
N-end bearing: insulated motor non-drive end bearing
N
Motors of this power range are not available as standard units. Consult the motor manufacturer.
n.a.
68 Guidelines for planning the electrical installation
Summary of Contents for ACS880-07CLC
Page 1: ...ABB industrial drives Hardware manual ACS880 07CLC drives ...
Page 2: ......
Page 4: ......
Page 64: ...64 ...
Page 82: ...82 ...
Page 91: ...PE PE 10 13 12 22 Electrical installation 91 ...
Page 122: ...122 ...
Page 124: ...124 ...
Page 132: ...5 4 11 7 6 8 132 Maintenance ...
Page 133: ...14 15 16 12 13 17 Maintenance 133 ...
Page 141: ...5 Set the real time clock Maintenance 141 ...
Page 142: ...142 ...
Page 150: ...150 ...
Page 176: ...ACS880 07CLC 0390A 7 C121 marine construction 176 Dimensions ...
Page 177: ...ACS880 07CLC 1310A 7 Dimensions 177 ...
Page 178: ...ACS880 07CLC 2180A 7 C121 marine construction 178 Dimensions ...
Page 179: ...ACS880 07CLC 3260A 7 C121 marine construction Dimensions 179 ...
Page 181: ... 2 D8D Dimensions 181 ...
Page 182: ... 3 D8D 182 Dimensions ...
Page 183: ... 4 D8D Dimensions 183 ...
Page 185: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 185 ...
Page 186: ...Inverter module cubicle with three R8i modules bottom cable exit 186 Dimensions ...
Page 187: ...Brake chopper cubicle D150 Dimensions 187 ...
Page 188: ...188 ...
Page 202: ...202 ...
Page 211: ......
Page 212: ......
Page 214: ...Contact us www abb com drives 3AXD50000131457 Rev A EN EFFECTIVE 2018 03 09 3AXD50000131457A ...