AI1 or AI2 as a Pt100, Pt1000, PTC or KTY84 sensor input
Three Pt100/Pt1000 sensors or one KTY84 sensor for motor temperature measurement
can be connected between an analog input and output as shown below. (Alternatively, you
can connect the KTY to an FIO-11 or FAIO-01 analog I/O extension module or FEN-xx
encoder interface module.) At the sensor end of the cable, leave the shields unconnected
or ground them indirectly via a high-frequency capacitor with a few nanofarads, eg. 3.3 nF
/ 630 V. The shield can also be grounded directly at both ends if they are in the same ground
line with no significant voltage drop between the end points.
XAI
XAO
AIn+
AIn-
AOn
AGND
1)
2)
T
T
T
1
…
3 × Pt100/Pt1000/PTC or 1 × KTY84
1)
Set the input type to voltage with the appropriate switch or jumper on the inverter control
unit. Make the corresponding setting in the inverter unit control program in parameter group
12 Standard AI
.
2)
Select the excitation mode in parameter group
13 Standard AO
of inverter unit control
program.
WARNING!
As the inputs pictured above are not insulated according to IEC/EN 60664, the
connection of the motor temperature sensor requires double or reinforced insulation
between motor live parts and the sensor. If the assembly does not fulfill the
requirement, the I/O board terminals must be protected against contact and must
not be connected to other equipment or the temperature sensor must be isolated
from the I/O terminals.
■
DIIL input
The DIIL input is used for the connection of safety circuits. The input is parametrized to stop
the unit when the input signal is lost.
■
Drive-to-drive link (XD2D)
Note:
On the ACS880-07CLC, the XD2D connector on the supply control unit (A51) is reserved
for cooling fan monitoring. See the
ACS880 distributed I/O bus
supplement
(3AXD50000126880 [English]).
The drive-to-drive link is a daisy-chained RS-485 transmission line that allows basic
master/follower communication with one master drive and multiple followers.
Control units of the drive 111
Summary of Contents for ACS880-07CLC
Page 1: ...ABB industrial drives Hardware manual ACS880 07CLC drives ...
Page 2: ......
Page 4: ......
Page 64: ...64 ...
Page 82: ...82 ...
Page 91: ...PE PE 10 13 12 22 Electrical installation 91 ...
Page 122: ...122 ...
Page 124: ...124 ...
Page 132: ...5 4 11 7 6 8 132 Maintenance ...
Page 133: ...14 15 16 12 13 17 Maintenance 133 ...
Page 141: ...5 Set the real time clock Maintenance 141 ...
Page 142: ...142 ...
Page 150: ...150 ...
Page 176: ...ACS880 07CLC 0390A 7 C121 marine construction 176 Dimensions ...
Page 177: ...ACS880 07CLC 1310A 7 Dimensions 177 ...
Page 178: ...ACS880 07CLC 2180A 7 C121 marine construction 178 Dimensions ...
Page 179: ...ACS880 07CLC 3260A 7 C121 marine construction Dimensions 179 ...
Page 181: ... 2 D8D Dimensions 181 ...
Page 182: ... 3 D8D 182 Dimensions ...
Page 183: ... 4 D8D Dimensions 183 ...
Page 185: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 185 ...
Page 186: ...Inverter module cubicle with three R8i modules bottom cable exit 186 Dimensions ...
Page 187: ...Brake chopper cubicle D150 Dimensions 187 ...
Page 188: ...188 ...
Page 202: ...202 ...
Page 211: ......
Page 212: ......
Page 214: ...Contact us www abb com drives 3AXD50000131457 Rev A EN EFFECTIVE 2018 03 09 3AXD50000131457A ...