Maintenance intervals
As a general rule, the quality of the coolant should be checked at intervals of two years.
This can be done by distributors of Antifrogen® L (see
) if a 250 milliliter
sample is provided.
Technical data
■
Coolant specification
Coolant type
Antifrogen® L (by Clariant International Ltd,
), mixed with water.
Ready-mixed coolant is available from Clariant distributors and ABB Service representatives.
The standard Antifrogen® L / water solution of 25/75% (volume) is usable down to a storage
temperature of -16 °C (3.2 °F). 50/50% coolant is optionally available for storage temperatures
down to -40 °C (-40 °F). Note that operation below 0 °C (32 °F) is not allowed regardless
of the freezing point of the coolant.
WARNING!
The warranty does not cover damage occurring from use of improper coolant.
■
Temperature limits
Ambient temperature:
See the technical data of the drive/unit.
Freeze protection:
The freezing point of the coolant is determined by the concentration of
heat transfer fluid in the mixture.
The higher the concentration of heat transfer fluid, the higher the viscosity of the coolant.
This results in a higher pressure loss in the system. An operating pressure of more than
150 kPa is required for sufficient flow.
The nominal current ratings of drive system modules apply to an Antifrogen® L / water
solution of 25/75% (volume). For derating with other ratios, contact your local ABB
representative.
Incoming coolant temperature:
•
4…40 °C (39…104 °F): no drive output current derating required
•
40…45 °C (104…113 °F): drive output current must be derated by 2 percentage points
per 1 °C (1.8 °F) temperature increase, as shown by curve (a).
•
45…50 °C (113…122 °F):
•
If components with a maximum operating temperature of 55 °C (131 °F) are installed
in the same space as the drive modules, drive output current must be derated by
6 percentage points per 1 °C (1.8 °F) temperature increase, as shown by curve (c).
•
If there are no components with a maximum operating temperature of 55 °C (131
°F) installed in the same space as the drive modules, drive output current must be
derated by 2 percentage points per 1 °C (1.8 °F) temperature increase, as shown
by curve (b).
The drawing below shows the derating factor (k) in relation to coolant temperature.
Internal cooling circuit 147
Summary of Contents for ACS880-07CLC
Page 1: ...ABB industrial drives Hardware manual ACS880 07CLC drives ...
Page 2: ......
Page 4: ......
Page 64: ...64 ...
Page 82: ...82 ...
Page 91: ...PE PE 10 13 12 22 Electrical installation 91 ...
Page 122: ...122 ...
Page 124: ...124 ...
Page 132: ...5 4 11 7 6 8 132 Maintenance ...
Page 133: ...14 15 16 12 13 17 Maintenance 133 ...
Page 141: ...5 Set the real time clock Maintenance 141 ...
Page 142: ...142 ...
Page 150: ...150 ...
Page 176: ...ACS880 07CLC 0390A 7 C121 marine construction 176 Dimensions ...
Page 177: ...ACS880 07CLC 1310A 7 Dimensions 177 ...
Page 178: ...ACS880 07CLC 2180A 7 C121 marine construction 178 Dimensions ...
Page 179: ...ACS880 07CLC 3260A 7 C121 marine construction Dimensions 179 ...
Page 181: ... 2 D8D Dimensions 181 ...
Page 182: ... 3 D8D 182 Dimensions ...
Page 183: ... 4 D8D Dimensions 183 ...
Page 185: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 185 ...
Page 186: ...Inverter module cubicle with three R8i modules bottom cable exit 186 Dimensions ...
Page 187: ...Brake chopper cubicle D150 Dimensions 187 ...
Page 188: ...188 ...
Page 202: ...202 ...
Page 211: ......
Page 212: ......
Page 214: ...Contact us www abb com drives 3AXD50000131457 Rev A EN EFFECTIVE 2018 03 09 3AXD50000131457A ...