Planning the electrical installation 63
Additional note for sine filters
Sine filters protect the motor insulation system. Therefore, du/dt filter can be replaced
with a sine filter. The peak phase-to-phase voltage with the sine filter is approximately
1.5 ·
U
N
.
Selecting the power cables
General rules
Select the input power and motor cables
according to local regulations
:
• Select a cable capable of carrying the drive nominal current. See section
(page
) for the rated currents.
• Select a cable rated for at least 70
°
C maximum permissible temperature of
conductor in continuous use. For US, see
page
.
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 V AC cable is accepted for up to 500 V AC. 750 V AC cable is accepted for
up to 600 V AC. For 690 V AC rated equipment, the rated voltage between the
conductors of the cable should be at least 1 kV.
Use symmetrical shielded motor cable (see page
) for drive frame size R5 and
larger, or motors larger than 30 kW (40 hp). A four-conductor system can be used up
to frame size R4 with up to 30 kW (40 hp) motors, but shielded symmetrical motor
cable is always recommended. Ground motor cable shields 360° at both ends. Keep
the motor cable and its PE pigtail (twisted shield) as short as possible to reduce high-
frequency electromagnetic emissions.
Note:
When continuous metal conduit is employed, shielded cable is not required.
The conduit must have bonding at both ends.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended.
Compared to a four-conductor system, the use of symmetrical shielded cable reduces
electromagnetic emission of the whole drive system as well as the stress on motor
insulation, bearing currents and wear.
The protective conductor must always have an adequate conductivity. The table
below shows the minimum cross-sectional area related to the phase conductor size
according to IEC 61439-1 when the phase conductor and the protective conductor
are made of the same metal.
ACS880-01 HW.book Page 63 Monday, July 1, 2013 4:51 PM
Summary of Contents for ACS880-01 Series
Page 4: ...ACS880 01 HW book Page 4 Monday July 1 2013 4 51 PM...
Page 12: ...12 ACS880 01 HW book Page 12 Monday July 1 2013 4 51 PM...
Page 20: ...20 Safety instructions ACS880 01 HW book Page 20 Monday July 1 2013 4 51 PM...
Page 26: ...26 Introduction to the manual ACS880 01 HW book Page 26 Monday July 1 2013 4 51 PM...
Page 80: ...80 Planning the electrical installation ACS880 01 HW book Page 80 Monday July 1 2013 4 51 PM...
Page 96: ...96 Electrical installation 8b R8 R9 ACS880 01 HW book Page 96 Monday July 1 2013 4 51 PM...
Page 98: ...98 Electrical installation 16 13 R8 R9 ACS880 01 HW book Page 98 Monday July 1 2013 4 51 PM...
Page 118: ...118 Start up ACS880 01 HW book Page 118 Monday July 1 2013 4 51 PM...
Page 120: ...120 Fault tracing ACS880 01 HW book Page 120 Monday July 1 2013 4 51 PM...
Page 131: ...Maintenance 131 3 4 5 3 ACS880 01 HW book Page 131 Monday July 1 2013 4 51 PM...
Page 172: ...172 Technical data ACS880 01 HW book Page 172 Monday July 1 2013 4 51 PM...
Page 196: ...196 Dimension drawings ACS880 01 HW book Page 196 Monday July 1 2013 4 51 PM...
Page 209: ...Safe Torque off function 209 Certificate ACS880 01 HW book Page 209 Monday July 1 2013 4 51 PM...
Page 210: ...210 Safe Torque off function ACS880 01 HW book Page 210 Monday July 1 2013 4 51 PM...
Page 220: ...220 Resistor braking ACS880 01 HW book Page 220 Monday July 1 2013 4 51 PM...