![ABB ACS880-01 Series Hardware Manual Download Page 204](http://html1.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_hardware-manual_3431303204.webp)
204 Safe Torque off function
Acceptance test procedure
After wiring the Safe torque off function, validate its operation as follows. Setting of
the control program parameters is not needed. If an FSO-xx safety functions module
is installed, refer to its documentation.
Action
WARNING!
Follow the
, page
. Ignoring the instructions
can cause physical injury or death, or damage to the equipment.
Ensure that the drive can be run and stopped freely during start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the
power line by a disconnector.
Check the Safe torque off (STO) circuit connections against the circuit diagram.
Close the disconnector and switch the power on.
Test the operation of the STO function when the motor is stopped.
• Give a stop command for the drive (if running) and wait until the motor shaft is at a
standstill.
Make sure that the drive operates as follows:
• Open the STO circuit. The drive generates an indication if one is defined for
‘stopped’ state in parameter 31.22 (see the firmware manual).
• Give a start command to verify that the STO function blocks the drive operations.
The motor should not start.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the STO function when the motor is running:
• Start the drive and make sure the motor is running.
• Open the STO circuit. The motor should stop. The drive generates an indication if
one is defined for ‘running’ state in parameter 31.22 (see the firmware manual).
• Reset any active faults and try to start the drive.
• Make sure that the motor stays at standstill and the drive operates as described
above in testing the operation when the motor is stopped.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
Document and sign the acceptance test report which verifies that the safety function is
safe and accepted for operation.
ACS880-01 HW.book Page 204 Monday, July 1, 2013 4:51 PM
Summary of Contents for ACS880-01 Series
Page 4: ...ACS880 01 HW book Page 4 Monday July 1 2013 4 51 PM...
Page 12: ...12 ACS880 01 HW book Page 12 Monday July 1 2013 4 51 PM...
Page 20: ...20 Safety instructions ACS880 01 HW book Page 20 Monday July 1 2013 4 51 PM...
Page 26: ...26 Introduction to the manual ACS880 01 HW book Page 26 Monday July 1 2013 4 51 PM...
Page 80: ...80 Planning the electrical installation ACS880 01 HW book Page 80 Monday July 1 2013 4 51 PM...
Page 96: ...96 Electrical installation 8b R8 R9 ACS880 01 HW book Page 96 Monday July 1 2013 4 51 PM...
Page 98: ...98 Electrical installation 16 13 R8 R9 ACS880 01 HW book Page 98 Monday July 1 2013 4 51 PM...
Page 118: ...118 Start up ACS880 01 HW book Page 118 Monday July 1 2013 4 51 PM...
Page 120: ...120 Fault tracing ACS880 01 HW book Page 120 Monday July 1 2013 4 51 PM...
Page 131: ...Maintenance 131 3 4 5 3 ACS880 01 HW book Page 131 Monday July 1 2013 4 51 PM...
Page 172: ...172 Technical data ACS880 01 HW book Page 172 Monday July 1 2013 4 51 PM...
Page 196: ...196 Dimension drawings ACS880 01 HW book Page 196 Monday July 1 2013 4 51 PM...
Page 209: ...Safe Torque off function 209 Certificate ACS880 01 HW book Page 209 Monday July 1 2013 4 51 PM...
Page 210: ...210 Safe Torque off function ACS880 01 HW book Page 210 Monday July 1 2013 4 51 PM...
Page 220: ...220 Resistor braking ACS880 01 HW book Page 220 Monday July 1 2013 4 51 PM...