Planning the electrical installation
48
Ground fault protection
The drive is equipped with an internal ground fault protective function to protect the
unit against ground faults in the motor and motor cable. This is not a personal safety
or a fire protection feature. The ground fault protective function can be disabled with
a parameter, refer to the appropriate
ACS800 Firmware Manual
.
The EMC filter of the drive includes capacitors connected between the main circuit
and the frame. These capacitors and long motor cables increase the ground leakage
current and may cause fault current circuit breakers to function.
Emergency stop devices
For safety reasons, install the emergency stop devices at each operator control
station and at other operating stations where emergency stop may be needed.
Note:
Pressing the stop key (
) on the control panel of the drive does not generate
an emergency stop of the motor or separate the drive from dangerous potential.
An emergency stop function is optionally available for stopping and switching off the
whole drive. Two stop categories according to IEC/EN 60204-1:1997 are available:
immediate removal of power (Category 0 for ACS800-07/U7) and controlled
emergency stop (Category 1 for ACS800-07/U7).
Restarting after an emergency stop
After an emergency stop, the emergency stop button must be released and the drive
started by turning the operating switch of the drive from position “ON” to “START”.
Power-loss ride-through function
The power-loss ride-through function is activated when parameter
20.06 UNDERVOLTAGE CTRL is set to ON (default in Standard Control Program).
ACS800-07/U7 units with line contactor (+F250)
The power-loss ride-through function is enabled by connecting RMIO board
terminals X22:8 and X22:11 with a jumper.
X22
1
2
3
4
5
6
7
8
9
10
11
X2 / RMIO board
K13
21
22
Summary of Contents for ACS800-U7
Page 1: ...ACS800 Hardware Manual ACS800 07 Drives 45 to 560 kW ACS800 U7 Drives 50 to 600 hp ...
Page 4: ......
Page 28: ...Operation principle and hardware description 28 ...
Page 51: ...Planning the electrical installation 51 ...
Page 60: ...Planning the electrical installation 60 ...
Page 76: ...Electrical installation 76 ...
Page 84: ...Motor control and I O board RMIO 84 ...
Page 112: ...Maintenance 112 ...
Page 138: ...Dimensional drawings 138 Frame sizes R5 and R6 64778340_1 5 K ...
Page 139: ...Dimensional drawings 139 Frame sizes R7 and R8 68749930_1 7 C ...
Page 140: ...Dimensional drawings 140 IP54 and IP54R units of frame sizes R7 and R8 68749930_6 6 C ...
Page 148: ...3AFE64702165 Rev H EN 2012 09 19 Contact us www abb com drives www abb com drivespartners ...