Planning the electrical installation
47
Protection against short-circuit inside the drive or in the supply cable
Arrange the protection according to the following guide lines.
1) Size the fuses according to instructions given in chapter
Technical data
.
The fuses will protect the input
cable in short-circuit situations, restrict drive damage and prevent damage to adjoining equipment in
case of a short-circuit inside the drive.
2) Circuit breakers which have been tested by ABB with the ACS800 can be used. Fuses must be used
with other circuit breakers. Contact your local ABB representative for the approved breaker types and
supply network characteristics.
The protective characteristics of circuit breakers depend on the type, construction and settings of the
breakers. There are also limitations pertaining to the short-circuit capacity of the supply network.
WARNING!
Due to the inherent operating principle and construction of circuit breakers,
independent of the manufacturer, hot ionized gases may escape from the breaker
enclosure in case of a short-circuit. To ensure safe use, special attention must be paid to
the installation and placement of the breakers. Follow the manufacturer’s instructions.
Note:
Circuit breakers must not be used without fuses in the USA.
3) Size the fuses according to local safety regulations, appropriate input voltage and the rated current of
the drive (see chapter
Technical data)
.
4) ACS800-07 units with enclosure extension are equipped with aR fuses as standard. ACS800-U7 units
are equipped with T/L fuses as standard. The fuses restrict drive damage and prevent damage to
adjoining equipment in case of a short-circuit inside the drive.
Circuit diagram
Drive type
Short-circuit
protection
DRIVE IS EQUIPPED WITH INPUT FUSES
ACS800-07
ACS800-U7
Protect the input cable
with fuses or a circuit
breaker according to
local regulations. See
footnotes 3) and 4).
Drive
Distribution
board
Input cable
~
~
M
3~
Drive
~
~
M
3~
3)
4)
4)
I
>
Summary of Contents for ACS800-U7
Page 1: ...ACS800 Hardware Manual ACS800 07 Drives 45 to 560 kW ACS800 U7 Drives 50 to 600 hp ...
Page 4: ......
Page 28: ...Operation principle and hardware description 28 ...
Page 51: ...Planning the electrical installation 51 ...
Page 60: ...Planning the electrical installation 60 ...
Page 76: ...Electrical installation 76 ...
Page 84: ...Motor control and I O board RMIO 84 ...
Page 112: ...Maintenance 112 ...
Page 138: ...Dimensional drawings 138 Frame sizes R5 and R6 64778340_1 5 K ...
Page 139: ...Dimensional drawings 139 Frame sizes R7 and R8 68749930_1 7 C ...
Page 140: ...Dimensional drawings 140 IP54 and IP54R units of frame sizes R7 and R8 68749930_6 6 C ...
Page 148: ...3AFE64702165 Rev H EN 2012 09 19 Contact us www abb com drives www abb com drivespartners ...