Planning the electrical installation
44
Additional data for calculating the rise time and the peak line-to-line voltage
If you need to calculate the actual peak voltage and voltage rise time considering the
actual cable length, proceed as follows:
• Peak line-to line voltage: Read the relative
Û
LL
/
U
N
value from the appropriate
diagram below and multiply it by the nominal supply voltage (
U
N
).
• Voltage rise time: Read the relative values
Û
LL
/
U
N
and (du/dt)/U
N
from the
appropriate diagram below. Multiply the values by the nominal supply voltage
(U
N
) and substitute into equation
t
= 0.8 ·
Û
LL
/(du/dt).
Additional note for sine filters
Sine filters protect the motor insulation system. Therefore, du/dt filter can be
replaced with a sine filter. The peak phase-to-phase voltage with the sine filter is
approximately 1.5 ·
U
N
.
Additional note for common mode filters
Common mode filter is available as a plus code option (+E208) or as a separate kit
(one box including three rings for one cable).
A
Drive with du/dt filter
B
Drive without du/dt filter
I
Motor cable length
Û
LL
/
U
N
Relative peak line-to-line voltage
(du/dt)/U
N
Relative du/dt value
Note
: ÛLL and du/dt values are approximately 20% higher with resistor braking.
Û
LL
/
U
N
l
(m)
du/dt
UN
-------------(1/
s)
1.0
2.0
5.0
4.0
3.0
1.5
2.5
3.5
4.5
100
200
300
100
200
300
0.0
0.5
1.0
1.5
2.0
2.5
3.0
l
(m)
du/dt
UN
-------------(1/
s)
Û
LL
/
U
N
5.5
A
B
Summary of Contents for ACS800-U7
Page 1: ...ACS800 Hardware Manual ACS800 07 Drives 45 to 560 kW ACS800 U7 Drives 50 to 600 hp ...
Page 4: ......
Page 28: ...Operation principle and hardware description 28 ...
Page 51: ...Planning the electrical installation 51 ...
Page 60: ...Planning the electrical installation 60 ...
Page 76: ...Electrical installation 76 ...
Page 84: ...Motor control and I O board RMIO 84 ...
Page 112: ...Maintenance 112 ...
Page 138: ...Dimensional drawings 138 Frame sizes R5 and R6 64778340_1 5 K ...
Page 139: ...Dimensional drawings 139 Frame sizes R7 and R8 68749930_1 7 C ...
Page 140: ...Dimensional drawings 140 IP54 and IP54R units of frame sizes R7 and R8 68749930_6 6 C ...
Page 148: ...3AFE64702165 Rev H EN 2012 09 19 Contact us www abb com drives www abb com drivespartners ...