Technical data
116
Fuses
The drive is equipped with aR fuses as standard. Standard aR fuses and optional gG
fuses for protection against short-circuit in the input power cable or drive are listed
below. Either fuse type may be used if it operates rapidly enough. Choose between
gG and aR fuses according to the table under
Quick guide for selecting between gG
and aR fuses
on page
120,
or verify the operating time by
checking that the short-
circuit current of the installation is at least the value given in the fuse table
.
The short-circuit current can be calculated as follows:
where
I
k2-ph
= short-circuit current in symmetrical two-phase short-circuit
U
= network line-to-line voltage (V)
R
c
= cable resistance (ohm)
Z
k
= z
k
·
U
N
2
/
S
N
= transformer impedance (ohm)
z
k
= transformer impedance (%)
U
N
= transformer rated voltage (V)
S
N
= nominal apparent power of the transformer (kVA)
X
c
= cable reactance (ohm).
Calculation example
Drive:
•
ACS800-07-0260-3
•
supply voltage
U
= 410 V
Transformer:
•
rated power
S
N
= 3000 kVA
•
rated voltage (drive supply voltage)
U
N
= 430 V
•
transformer impedance z
k
= 7.2%.
I
k2-ph
=
2
·
R
c
2
+ (
Z
k
+
X
c
)
2
U
Summary of Contents for ACS800-U7
Page 1: ...ACS800 Hardware Manual ACS800 07 Drives 45 to 560 kW ACS800 U7 Drives 50 to 600 hp ...
Page 4: ......
Page 28: ...Operation principle and hardware description 28 ...
Page 51: ...Planning the electrical installation 51 ...
Page 60: ...Planning the electrical installation 60 ...
Page 76: ...Electrical installation 76 ...
Page 84: ...Motor control and I O board RMIO 84 ...
Page 112: ...Maintenance 112 ...
Page 138: ...Dimensional drawings 138 Frame sizes R5 and R6 64778340_1 5 K ...
Page 139: ...Dimensional drawings 139 Frame sizes R7 and R8 68749930_1 7 C ...
Page 140: ...Dimensional drawings 140 IP54 and IP54R units of frame sizes R7 and R8 68749930_6 6 C ...
Page 148: ...3AFE64702165 Rev H EN 2012 09 19 Contact us www abb com drives www abb com drivespartners ...