Technical data
130
Cooling
Method
Internal fan, flow direction from front to top
Filter material
Inlet (door)
Outlet (roof)
IP22 / IP42 units
airTex G150
288 mm x 292 mm
688 mm x 521 mm
-
IP54 units
Luftfilter/airComp 300-50
288 mm x 292 mm
688 mm x 521 mm
Luftfilter/airTex G150
2 pcs: 398 mm x 312 mm
Free space around the unit
See
Free space around the unit
.
Cooling air flow
See
IEC data.
Degrees of protection
IP21 (UL type 1), IP22 (UL type 1), IP42 (UL type 2),
IP54 (UL type 12 for indoor use only), IP54R
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Operation
installed for stationary use
Storage
in the protective package
Transportation
in the protective package
Installation site altitude
0 to 4000 m (13123 ft) above
sea level [above 1000 m
(3281 ft), see section
Derating
].
Cabinets with Q968:
0 to 2000 m (6562 ft)
-
-
Air temperature
-15 to +50 °C (5 to 122 °F).
No frost allowed. See
section
Derating
.
-40 to +70 °C
(-40 to +158 °F)
-40 to +70 °C
(-40 to +158 °F)
Relative humidity
5 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
No conductive dust allowed.
Boards without coating:
Chemical gases: Class 3C1
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
Boards without coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards without coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Atmospheric pressure
70 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Vibration
(IEC 60068-2)
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz) sinusoidal
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz) sinusoidal
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
max. 15 m/s
2
(49 ft/s
2
)
(9 to 200 Hz) sinusoidal
Shock
(IEC 60068-2-27)
Not allowed
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Free fall
Not allowed
100 mm (4 in.) for weight
over 100 kg (220 lb)
100 mm (4 in.) for weight
over 100 kg (220 lb)
Summary of Contents for ACS800-U7
Page 1: ...ACS800 Hardware Manual ACS800 07 Drives 45 to 560 kW ACS800 U7 Drives 50 to 600 hp ...
Page 4: ......
Page 28: ...Operation principle and hardware description 28 ...
Page 51: ...Planning the electrical installation 51 ...
Page 60: ...Planning the electrical installation 60 ...
Page 76: ...Electrical installation 76 ...
Page 84: ...Motor control and I O board RMIO 84 ...
Page 112: ...Maintenance 112 ...
Page 138: ...Dimensional drawings 138 Frame sizes R5 and R6 64778340_1 5 K ...
Page 139: ...Dimensional drawings 139 Frame sizes R7 and R8 68749930_1 7 C ...
Page 140: ...Dimensional drawings 140 IP54 and IP54R units of frame sizes R7 and R8 68749930_6 6 C ...
Page 148: ...3AFE64702165 Rev H EN 2012 09 19 Contact us www abb com drives www abb com drivespartners ...