1.
Do not connect a high-power capacitor to the power line while the drive is connected.
The connection will cause voltage transients that may trip or even damage the drive.
2.
If capacitor load is increased/decreased step by step when the AC drive is connected
to the power line, make sure that the connection steps are low enough not to cause
voltage transients that would trip the drive.
3.
Make sure that the power factor compensation unit is suitable for use in systems with
AC drives, ie, harmonic generating loads. In such systems, the compensation unit should
typically be equipped with a blocking reactor or harmonic filter.
Using a safety switch between the drive and the motor
ABB recommends to install a safety switch between the permanent magnet motor and the
drive output. The switch is needed to isolate the motor from the drive during maintenance
work on the drive.
Implementing an ATEX-certified motor thermal protection
With Q971, the drive provides ATEX-certified safe motor disconnection without
contactor using the drive Safe torque off function. To implement the thermal protection of
a motor in explosive atmosphere (Ex motor), you must also:
•
use an ATEX-certified Ex motor
•
order an ATEX-certified thermistor protection module for the drive (L357), or
acquire and install an ATEX-compliant protection relay
•
do the necessary connections.
For more information, see:
Manual code
(English)
User's manual
CPTC-02 ATEX-certified thermistor protection module, Ex II (2) GD (L537+Q971)
user's manual
Controlling a contactor between drive and motor
The control of the output contactor depends on how you use the drive, that is, which motor
control mode and which motor stop mode you select.
If you have the vector control mode and motor ramp stop selected, open the contactor as
follows:
1.
Give a stop command to the drive.
2.
Wait until the drive decelerates the motor to zero speed.
3.
Open the contactor.
If you have the vector control mode and motor coast stop, or scalar control mode selected,
open the contactor as follows:
1.
Give a stop command to the drive.
2.
Open the contactor.
82 Guidelines for planning the electrical installation
Summary of Contents for ACH580-04
Page 1: ... ABB DRIVES FOR HVAC ACH580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 54: ...54 ...
Page 88: ...88 ...
Page 100: ...100 ...
Page 118: ...118 ...
Page 122: ...122 ...
Page 124: ...124 ...
Page 128: ...3 6 5 5 128 Maintenance ...
Page 134: ...134 ...
Page 156: ...R10 standard configuration 156 Dimension drawings ...
Page 157: ...R10 with E208 0H354 H356 H370 0H371 Dimension drawings 157 ...
Page 158: ...R10 with option B051 158 Dimension drawings ...
Page 159: ...R10 with option E208 H356 P906 192 Tools R10 3 1 Dimension drawings 159 ...
Page 160: ...R10 with option E208 0H371 H356 0H354 H370 P906 Tools 191 R10 2 1 160 Dimension drawings ...
Page 161: ...R10 with option B051 P906 190 Tools R10 1 1 Dimension drawings 161 ...
Page 162: ...R11 standard configuration 162 Dimension drawings ...
Page 163: ...R11 with option E208 0H371 H356 0H354 H370 Dimension drawings 163 ...
Page 164: ...R11 with option B051 164 Dimension drawings ...
Page 165: ...R11 with option E208 H356 P906 Dimension drawings 165 ...
Page 166: ...R11 with option E208 0H371 H356 0H354 H370 P906 166 Dimension drawings ...
Page 167: ...R11 with option B051 P906 Dimension drawings 167 ...
Page 186: ... Declaration of conformity 186 The Safe torque off function ...
Page 206: ...Dimension drawing 206 External control unit option P906 ...
Page 212: ...212 ...
Page 224: ...224 ...
Page 226: ...226 ...
Page 234: ...234 ...