Configuring the Thermostat
Product Manual 2CQA 100 014 B0001
│
2018-09-28
│
10
Setting
Description
Options
Image
•
Manual (active
open)
•
Manual (active
closed)
Compressor
delay between
cycles [s]
Note:
Only if air-
conditioner or heat
pump exists.
Setting defines
minimum time
system must wait
before air-conditioner
or heat pump can
run again.
120 to 360
in increments of 10
Fan timer
after heating
[s]
Note:
Not for water-
based systems.
Defines fan-running
time after heating
has switched off.
During time
remaining heat in
system is extracted.
60 to 240
in increments of 10
Fan timer
after cooling
[s]
Note:
Not for water-
based systems.
Defines fan-running
time after air
conditioning has
switched OFF. This
allows system to
distribute remaining
pre-cooled air
already present in
ducts.
60 to 240
in increments of 10
Minimum ON
time for gas
furnace [s]
Note:
Only for gas
furnaces.
Setting defines
minimum time gas
furnace stays ON.
Some gas furnaces
should not be
switched ON/OFF
rapidly to prevent
damage or
premature wear of
parts.
0 to 240
in increments of 10
Fan delay ON
cooling [s]
Note:
Not for water-
based systems.
Delays time for fan
after cooling starts.
Prevents warm air
coming out of vent
while air conditioning
is still cooling.
0 to 240
in increments of 10