EC2-391_65136_EN_R01.doc 

Replacement for 00 

1 / 4  

PCN: 865 022       21.09.2007 

 

 

EC2-391 Display Case and Coldroom Controller 

Operating Instructions 

GB 

Note: This document contains short form instructions for experienced users. 
Use last column in List of Parameters to document your individual settings. 
More detailed information can be found in the User Manual.  

 

The EC2-391 is a dedicated refrigeration controller with superheat and a driver for 
an Alco Controls Electric Control Valve EX2. In addition the EC2-391 controls air 
temperature and manages defrost and fan(s). 
 

 

 

Two ECN-Pxx pipe temperature sensors (1) and (2) measure suction gas 
temperatures at the evaporator inlet / outlet and feed the signals into the superheat 
control loop. The superheat controller output modulates the opening of the EX2 
pulse width modulated Electrical Control Valve (6) thus optimising the refrigerant 
mass flow through the evaporator. The air temperature sensors (3) and (4) measure 
air-in and out temperature of the evaporator and feed signals into the air 
temperature thermostat. The ECN-Fxx fin sensor (5) is used for defrost 
termination. The controller has 3 relay outputs to control the defrost heater (9), the 
evaporator fan (8) and an optional output

 

(7). Please consult the technical data 

(right) for input and output ratings. 
In case of power loss, due to the positive shut-off characteristics of the EX2 
Electrical Control Valves, a liquid line solenoid valve is not needed to prevent 
flooding of the compressor.  

!

  Safety instructions:  

 

Read installation instructions thoroughly. Failure to comply can result in 
device failure, system damage or personal injury. 

 

The product is intended for use by persons having the appropriate 
knowledge and skills.  

 

Ensure electrical ratings per technical data are not exceeded.  

 

Disconnect all voltages from system before installation. 

 

Keep temperatures within nominal limits.  

 

Comply with local electrical regulations when wiring 

Technical Data

 

EC2 Series Controller 

Power supply 

24VAC ±10%; 50/60Hz; Class II 

Power consumption 

20VA max including EX2 

Communication LonWorks® 

Interface, FTT10, RJ45 connector 

Plug-in connector size 

Removable screw terminals 
wire size 0.14 … 1.5mm

2

 

Temperature 
     storage 
     operating 

 
   -20 … +65°C 
 

0 … +60°C 

Humidity 

0…80% r.h.  non condensing 

Protection class 

IP65 (front protection with gasket) 

Pressure transmitter input 

24VDC, 4...20mA 

Output relays               (3) 

SPDT contacts, AgCdO 

 Inductive 

(AC15) 

250V/2A 

 

Resistive (AC1) 250V/8A; 12A total return current 

Triac output for EX2 
Electrical Control Valve 
Coil (ASC 24V only) 

24V AC, 0.1 … 1A  

Marking 

  

 

Mounting 

The EC2-391 can be mounted in panels with a 71 x 
29 mm cutout. See dimensional drawing below for 
space requirements including rear connectors. 
Push controller into panel cutout.(1) 
Make sure that mounting lugs are flush with outside 
of controller housing 
Insert allen key into front panel holes and turn 
clockwise. Mounting lugs will turn and gradually 
move towards panel (2) 
Turn allen key until mounting lug barely touches 
panel. Then move other mounting lug to the same 
position (3) 
Tighten both sides very carefully until controller is 
secured. Do not over tighten as mounting lugs will 
break easily. 
 

 

 

Electrical Installation 

Refer to the electrical wiring diagram (below) for electrical connections. A copy of 
this diagram is labeled on the controller. Use connection wires/cables suitable for 
90°C operation (EN 60730-1). 

 

EC2 analog inputs are for dedicated sensors only and should not be connected to 
any other devices. 

Important:

 Keep controller and sensor wiring well separated 

from mains wiring. Minimum recommended distance 30mm.

  

Warning:

 Use a class II category transformer for 24VAC power supply 

(EN 60742). Do not ground the 24VAC lines. We recommend to use one 
transformer per EC2 controller and to use separate transformers for 3

rd

 party 

controllers, to avoid possible interference or grounding problems in the power 
supply. Connecting any EC2 inputs to mains voltage will permanently damage the 
EC2. 
 

 

Summary of Contents for EC2-391

Page 1: ... Comply with local electrical regulations when wiring Technical Data EC2 Series Controller Power supply 24VAC 10 50 60Hz Class II Power consumption 20VA max including EX2 Communication LonWorks Interface FTT10 RJ45 connector Plug in connector size Removable screw terminals wire size 0 14 1 5mm2 Temperature storage operating 20 65 C 0 60 C Humidity 0 80 r h non condensing Protection class IP65 fron...

Page 2: ... value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press PRG to confirm the new values and exit the parameters modification procedure To exit without modifying any parameter Do not press any button for at least 60 seconds TIME OUT Press ESC on IR remote control Defrost Activation A defrost cycle can be activated locally from the k...

Page 3: ...ion sensor 0 1 1 0 Dedicated defrost sensor must be installed 1 Air out sensor used for defrost termination d3 Pulsed defrost 0 1 0 0 off no pulsed defrost heaters switched off at defrost termination temperature dt or max time dP whatever is selected 1 on pulsed defrost dd and dH in use heaters are switched off at dH and switched on again at dH dd d4 Defrost at startup 0 no 1 yes 0 1 0 d5 Delay po...

Page 4: ...or a second wink request is received OF Node is offline The node is offline and no application is running This is the result of a network management command and will happen for example during node installation dS Defrost standby dP Pump down dF Defrost cycle dd Defrost drain delay dI Defrost injection delay du Defrost start up delay Cn Cleaning CL Alarms are cleared Visualising Data LON Monitoring...

Reviews: