EC2-391 Display Case and Coldroom Controller 

Operating Instructions 

GB 

List of Parameters 

 

/ DISPLAY 

PARAMETERS 

Min Max

 

Unit Def. Custom

/1  Value to show 

0   

  0 = Thermostat control temperature with Temp. alignment °C 

1 = Air-in temperature °C 
2 = Air-out temperature °C 
3 = Alarm temperature °C 
4 = Defrost termination temperature °C 
5 = Coil-in temperature °C  
6 = Coil-out temperature °C 
7 = Calculated superheat °K 
8 = Valve opening in % 
9 = Displays defrost status 

         

/2  Alarm suppression   0 = off, 1 = on 

0   

/5  Temperature Unit  

0 = °C, 1 = °F 

0   

/6  Decimal point  

0 = yes, 1 = no 

0   

/7  Display during defrost 

 

  0 = dF (= defrost mode);   1 = dF + defrost termination temp. 

 

2 = dF + control temperature 

       

 

/C  Temperature alignment  for /1=0 

-20 

20 

K / °F  0.0   

A ALARM-PARAMETERS 

 

 

 

 

 

A0  Mean factor alarm temperature 

100 

100   

A1  Low temp alarm delay 

180 

min 

5   

A2  High temp alarm delay 

180 

min 

5   

A3  Alarm delay after defrost 

180 

min 

10   

AH 

High temp alarm limit 

AL 

70 

°C / K 

40   

AL  Low temp alarm limit 

-55  AH  °C / K  -50   

At  Alarm limit type 

0   

  0=absolute temperatures °C; 1= relative temperatures K to setpoint          

r THERMOSTAT-PARAMETERS 

r1 Min setpoint 

-50  r2 

°C 

-50   

r2 Setpoint max 

r1  60 

°C 

40   

r3  Day/night control   

0 = off, 1 = on 

1   

r4 Thermostat mode 

1   

  0 = off, no thermostat function, continues cooling air in sensor monitoring 

off, no temp. alarms generated  

1 = cooling, deadband control: 

cut in   = set-point + difference   

 

cut out = set-point 

2 = cooling, modulating thermostat:  cut in   = set-point   

 

cut out = set-point – difference /2 

3 = heating, deadband control: 

cut in   = set-point – difference  

 

cut out = set-point 

4 = on, external control using nvi Valve via SNMP. Air in and air out sensor 
 

monitoring off. Temp. alarms will be generated 

 

r6 Setpoint night 

r1  r2 

°C 

4.0   

r7 Differential night 

0.1  20.0 

2.0   

r8  Mean factor, day operation 

100 

100 

 

r9  Mean factor, night operation 

100 

50 

 

rd Differential day 

0.1  20.0 

2.0   

St Setpoint day 

r1  r2 

°C 

2.0   

d DEFROST 

PARAMETERS 

 

 

 

 

 

d0 Defrost mode 

1   

  0 = natural defrost, defrost heater not activated 

pulsed defrost not possible 

1 = forced defrost, defrost heater activated, pulsed 

defrost possible 

2 = forced defrost, defrost heater activated, pulsed defrost possible, 

defrost termination using nviStartUp via SNMP 

         

d1  Termination by:  

0   

  0 = termination by temperature,  

termination by time will generate an alarm 

1 = termination by time,  

termination by temperature will generate an alarm 

2 = first, what ever comes first time or temperature, no alarm 
3 = last, by time and temperature, no alarm 

         

d2  Defrost termination sensor  

 

  0 = Dedicated defrost sensor must be installed 

1 = Air-out sensor used for defrost termination 

         

d3 Pulsed defrost 

0   

  0 = off, no pulsed defrost, heaters switched off at defrost termination 

temperature dt or max. time dP whatever is selected  

1 = on, pulsed defrost, dd and dH in use, heaters are switched off at 

dH and switched on again at  dH – dd 

         

d4  Defrost at startup  

0 = no, 1 = yes 

0   

d5  Delay power up defrost 

180 

min 

0   

 

   

Min

 

Max

 

Unit Def. Custom

d6 Pump down delay 

180 

sec 

0   

  Compressor will run during pump down delay while valve is closed           

d7 Drain delay 

15 

min 

2   

d8 Injection delay 

180 

sec 

0   

  Valve is open during injection delay while compressor is not running          

d9 Demand defrost mode 

0 = off, 1 = on, 2 = on together with 
timed defrost 

0 2  -  0 

 

dd Pulsed defrost differential 

20 

2   

dH Pulsed defrost setpoint 

-40 

dt 

°C 

5   

dt  Defrost termination temperature 

-40 

90 

°C 

8   

dP Max defrost duration 

180 

min 

30   

dI Defrost interval 

192 

8   

du Start up delay after synch 

180 

min 

30   

F FAN-PARAMETERS 

 

 

 

 

 

F1 Fan startup by:   

0 = on  

0   

  1 = delayed by time Fd, error on temperature 

2 = by temperature Ft, error on time 
3 = first, whatever comes first time or temperature, no alarm 
4 = last, time and temperature must come, no alarm 

         

F2 During no cooling  

0   

  0 = on; 1 = off; 2 = delayed by F4; 3 = off, when door open 

         

F3 During defrost  

0 = on, 1 = off 

0   

F4 Stop delay time  

30 

min 

0   

F5 During cleaning   

0 = off, 1 = on 

0   

Fd Fan delay after defrost 

30 

min 

0   

Ft On temp after defrost 

-40 

40 

°C 

0   

u SUPERHEAT 

PARAMETERS 

u0 Refrigerant  0 = R22 

1 = R134a  

2 = R507 

3 = R404A  4 = R407C  

5 = R410A  6 = R124 

7 = R744A 

0 7  -  3 

 

u1 Correction glide / dp 

Glide              = positive  values 
Pressure drop = negative values 

-20.0 20.0 

0.0   

u2 MOP control 

 

0 = MOP off, 1 = MOP on 

0 1  -  0 

 

u3 MOP temperature 

-40 

40 

°C 

0   

u4 Superheat mode  

0 = off 

1 = fixed superheat 
2 = adaptive superheat 

0 2  -  1 

 

u5 Superheat init setpoint 

u6 

u7 

6   

u6 Superheat setpoint min. 

u7 

3   

u7 Superheat setpoint max. 

u6 

20 

15   

uu Start 

opening 

25 

75 % 30 

 

 DIGITAL 

INPUT 

PARAMETERS 

i0  S5 input 

1 = inverse function 

0   

0 Functions for S5  0 = normal input 

0   

  1 = cleaning 

2 = only fan 
3 = door contact 
4 = permanent cooling 

5 = day / night switch 
6 = compressor safety chain 
7 = defrost request 
8 = defrost inhibited 

       

 DIGITAL 

OUTPUT 

PARAMETERS 

o0 Output 

1 = inverse function 

0   

n0 Functions for output  1 = alarm 

0   

H OTHER PARAMETERS 

 

 

 

 

 

H2 Display access 

 

3   

  0 = all disabled (Caution: access to controller only via LON 

network possible) 

1 = Keyboard enabled 
2 = IR remote control enabled 
3 = Keyboard and IR remote control; Temporary data display and 

manual defrost enabled. 

4 = Keyboard and IR remote control; Temporary data display 

disabled. Control setpoint with 

SEL

 key and manual defrost 

enabled. 

         

H3 IR access code 

199 

0   

H5 Password 0 

199 

12

 

 

 

Summary of Contents for EC2-391

Page 1: ... Comply with local electrical regulations when wiring Technical Data EC2 Series Controller Power supply 24VAC 10 50 60Hz Class II Power consumption 20VA max including EX2 Communication LonWorks Interface FTT10 RJ45 connector Plug in connector size Removable screw terminals wire size 0 14 1 5mm2 Temperature storage operating 20 65 C 0 60 C Humidity 0 80 r h non condensing Protection class IP65 fron...

Page 2: ... value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press PRG to confirm the new values and exit the parameters modification procedure To exit without modifying any parameter Do not press any button for at least 60 seconds TIME OUT Press ESC on IR remote control Defrost Activation A defrost cycle can be activated locally from the k...

Page 3: ...ion sensor 0 1 1 0 Dedicated defrost sensor must be installed 1 Air out sensor used for defrost termination d3 Pulsed defrost 0 1 0 0 off no pulsed defrost heaters switched off at defrost termination temperature dt or max time dP whatever is selected 1 on pulsed defrost dd and dH in use heaters are switched off at dH and switched on again at dH dd d4 Defrost at startup 0 no 1 yes 0 1 0 d5 Delay po...

Page 4: ...or a second wink request is received OF Node is offline The node is offline and no application is running This is the result of a network management command and will happen for example during node installation dS Defrost standby dP Pump down dF Defrost cycle dd Defrost drain delay dI Defrost injection delay du Defrost start up delay Cn Cleaning CL Alarms are cleared Visualising Data LON Monitoring...

Reviews: