domat UC100 

03/2017 Subject to technical changes.. 

 

 

 

UC100 

Communicative heating 
controller 

 

 

 

 

 

 

 

Summary 
 
 

UC100 is a communicative room heating controller with one PWM output for 
control of a radiator or electrical heater. It can work autonomously, or in 
connection to a primary controller (MiniPLC or SoftPLC), building management 
system (RcWare Vision or any SCADA), or to UCWEB 

 the web interface. 

 

Application 
 
 

 

Systems  with  radiators,  electric  heaters,  or  floor  heating 

  control  and 

measuring of room temperature 

 

monitoring and communication of room temperatures 
 

Function 
 
 

The  controller  reads  actual  room  temperature,  setpoint  shift  by  a  knob,  and  set 
operation  status  which  is  set  by  short  push  of  the  knob.  The  room  temperature  is 
measured in the range of -20 to +50 

°C. Measured and set values are processed in a PI 

algorithm,  at  the  output  of  which  there  is  a  PWM  controlled  triac.  All  values  are 
displayed on a large LCD display. 
 
The output works either as PWM controlled by a PI controller, or on/off (thermostat). 
The functionality and control parameters, i.e. P and I constants, and hysteresis, can be 
set  with 

ModComTool

,  the  configuration  software,  which  is  free  to  download  at

 

http://domat-int.com/en/downloads/software

. 

 
The controller contains real time clock with a weekly scheduler (6 events per day). It 
changes between three operation modes: Day, Night, and Off. A short push in the Night 
mode switches to Party mode 

 Comfort extension by 2 hours. 

 
The Change-over function (communicated over the bus) switches to the cooling mode 
while  cooling setpoints come  into effect. This mode  is used when  heat pumps with 
change-over mode are installed. The change-over signal is read from the heat pump 
interface  or  a  thermostat  at  the  supply  water  piping,  and  is  transmitted  to  the 
controllers  over  MiniPLC,  UCWEB,  or  any  Modbus  master.  See 

Room  units  and 

controllers, Communication protocol description

 handbook for register addressing and 

communication examples. 

Summary of Contents for UC100

Page 1: ...iac All values are displayed on a large LCD display The output works either as PWM controlled by a PI controller or on off thermostat The functionality and control parameters i e P and I constants and hysteresis can be set with ModComTool the configuration software which is free to download at http domat int com en downloads software The controller contains real time clock with a weekly scheduler ...

Page 2: ...0 Sensor accuracy 1 5 K with software correction Outputs 1x solid state relay zero switching for AC load 24 V AC max switching current 0 4A recommended thermic actuators are Siemens STA71 Danfoss TWA 24V types etc Setpoint correction according to configuration 10 to 1 K Communication 2 wire RS485 Modbus RTU slave optically separated Display LCD 60 x 60 mm Terminals screw terminals for 0 14 1 5 mm2...

Page 3: ...o not need any servicing or maintenance Install them in a vertical position at places where they can be operated easily and measure correct values of temperature i e in the height of about 150 cm with no direct sunlight or other heat cool source AHU outlets refridgerator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the...

Page 4: ...then follows the actual time schedule The weekly time schedule switches between Day Night and Off modes according to the event list There may be up to 6 events per day Time schedule settings Switch to the time schedule settings mode with a long push 1 s The controller switches to settings mode clock icon Turn the knob to select the weekday 1 to 7 Then short push to confirm the selection Turn the k...

Page 5: ...hing Setpoint temp Heating Off mode Temperature Heating Empty house are flashing Setpoint temp Cooling Day mode Temperature Cooling Day are flashing Setpoint temp Cooling Night mode Temperature Cooling Night are flashing Setpoint temp Cooling Off mode Temperature Cooling Empty house are flashing Select the requested value by a short push Turn knob to change value Confirm by a short push again If t...

Page 6: ...llers is about 50 m If the controllers and valves are at higher distance than 50 m from the transformer or more valves are connected to the transformer max 2 valves per controller it is more suitable to supply the controllers locally The RS485 bus is galvanically separated and connects all controllers regardless of the way they are powered Temperature compensation After switching the unit on allow...

Page 7: ...ubject to technical changes 7 Changes in version 08 2016 Changed the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours ...

Reviews: