Main Chiller Controller Technical Guide
APPENDIX B - BACnet
®
55
BACnet
®
Parameters
ANALOG INPUTS
BACnet
®
Point Name
Object
BACnet
®
Description
Limits
Application
Software Version
AI:1
Current version of the software in the unit.
Operating Mode
AI:2
Current Occupied/Startup Status
Off Mode (0)
Initial Start Delay (1)
Run Mode (2)
Leaving Water
Temperature
AI:3
Leaving Water Temperature
Leaving Water
Setpoint
AI:4
Current Leaving Water Temperature Setpoint
Entering Water
Temperature
AI:5
Entering Water Temperature
Outdoor Air
Temperature
AI:6
Outdoor Air Temperature
Vestibule
Temperature
AI:7
Vestibule Temperature
Barrel Refrigerant
Level
AI:8
Refrigerant Level in the Barrel
Barrel Level
Setpoint
AI:9
Current Barrel Refrigerant Level Operating Setpoint
Water Temperature
Reset Voltage
AI:10
Leaving Water Setpoint Reset Voltage Signal
Compressor Demand
Percent Signal
AI:11
Demand Signal to all Active Compressors
Liquid Line
Temperature
AI:12
Liquid Line Temperature
Liquid Line Pressure
AI:13
Liquid Line Pressure
Liquid Line
Saturation
Temperature
AI:14
Liquid Line Saturation Temperature
Liquid Line
Sub-cooling
AI:15
Liquid Line Sub-cooling Temperature
Evap Expansion
Valve Position
AI:16
Expansion Valve Position for Barrel Level
Condenser Fan
Speed
AI:17
Condenser Fan VFD Speed
Water Valve Position
AI:18
Water Valve Position
Economizer #1
Expansion Valve
AI:19
Economizer #1 Expansion Valve Position
Economizer #1
Suction Pressure
AI:20
Economizer #1 Suction Pressure
Economizer
#1 Saturation
Temperature
AI:21
Economizer #1 Saturation Temperature
Economizer #1
Suction Line
Temperature
AI:22
Economizer #1 Suction Line Temperature