Main Chiller Controller Technical Guide
APPENDIX A - COMPRESSOR CIRCUIT MODULE LED SCREENS
49
MIN SPD
XXXXRPM
MINIMUM COMPRESSOR SPEED FEEDBACK
RPMs from Turbocor
IGV PERCENTAGE
0-100%
IGV %
XXX
Turbocor Info Screens
Refer to the following map when navigating through the Turbo Info
Screens. From the TURBOCOR INFO Screen, press
<ENTER>
to
scroll through the screens.
TURBOCOR
INFO
BMC STAT
BMC STATE
BMC Operation Mode:
0=Standby, 1=Levitate, 2=Drive, 3=Calibrate
COMPRESSOR CONTROL STATUS
CONTROL MODE STATES
0 = Levitate Only Mode
1 = Manual Control Mode
2 = Analog Input Mode
3 = ModBus Network Mode
4 = Not Used
SYSTEM STATUS STATES
5 = Locked Out (power cycle required)
6 = IGV/EXV Reset Mode
7 = Ramping Up
8 = Partial Vane Operation
9 = Normal Operation
10 = Maximum Capacity
11 = Minimum IGV
12 = Interlock Open
13 = Fault Reset Mode
14 = Above Drive Temp - waiting to cool down
15 = Compressor Idle
COMPSTAT
BIT0-15=#
Turbocor Info Screen
MAX SPD
XXXXRPM
MAXIMUM COMPRESSOR SPEED FEEDBACK
RPMs from Turbocor
COMM T/O
#
COMM TIMEOUT TIMER
0 - 30 (if 30, Alarm & Fault)
3PH AMP
0
3-PHASE AMPERAGE
Three Phase Current Feedback reading
from the Turbocor compressor.