Main Chiller Controller Technical Guide
APPENDIX A - MAIN CHILLER CONTROLLER LCD SCREENS
43
DEVICEID
XXXXXXX
MSTP Baud
38400
BACnet
®
- CURRENT BAUD RATE
9600, 19200, 38400, 57600, 76800. Default is 38400.
EBUS
Lo Speed or
Hi Speed
E-BUS COMMUNICATIONS
Hi Speed or Lo Speed. Default is Hi Speed.
Settings Screens
BACnet
®
- CURRENT DEVICE ID
A Device ID of up to 7 digits can be entered.
The
<ENTER>
key moves the cursor between the digit fi elds starting
with the ones fi eld. Once the cursor is under a fi eld, use the
<UP>
&
<DOWN>
arrow keys to select a number between 0 and 9.
Settings Screens
Refer to the following map when navigating through the Settings
Screens. From the
Settings Screen
, press
<ENTER>
to scroll through
the screens.
Settings
MAC Addr
0 TO 127
BACnet
®
- CURRENT MAC ADDRESS
Valid range is 0 to 127. Default is 1.
The
<ENTER>
key moves the cursor between the digit fi elds starting
with the ones fi eld. Once the cursor is under a fi eld, use the
<UP>
&
<DOWN>
arrow keys to select a number between 0 and 9.
Unit ID#
Addr #1-59
UNIT ADDRESS
Unit address. Valid range is 1-59. Default is 59.
485 Baud
Lo-Speed or
Hi-Speed
BAUD RATE SPEED
485 baud rate speed. Valid range is Lo-Speed or Hi-Speed.
Default is Hi-Speed.