89
Appendix B - Thermistor Temperature vs. Resistance Values
Deg C
Deg F
Resistance (kOhms)
-40
-40
2889.6
-35
-31
2087.22
-30
-22
1522.20
-25
-13
1121.44
-20
-4
834.72
-15
5
627.28
-10
14
475.74
-5
23
363.99
0
32
280.82
5
41
218.41
10
50
171.17
15
59
135.14
20
68
107.44
25
77
86.00
30
86
69.28
35
95
56.16
40
104
45.81
45
113
37.58
50
122
30.99
55
131
25.68
60
140
21.40
65
149
17.91
Deg C
Deg F
Resistance (kOhms)
70
158
15.07
75
167
12.73
80
176
10.79
85
185
9.20
90
194
7.87
95
203
6.77
100
212
5.85
105
221
5.09
110
230
4.45
115
239
3.87
120
248
3.35
125
257
2.92
130
266
2.58
135
275
2.28
140
284
2.02
145
293
1.80
150
302
1.59
155
311
1.39
160
320
1.25
165
329
1.12
170
338
1.01
175
347
0.92
180
356
0.83
Summary of Contents for RQ SERIES
Page 2: ......
Page 29: ...29 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations ...
Page 43: ...43 Figure 21 Example 2 6 ton through the Base Gas Piping ...
Page 49: ...49 Figure 22 Post Corner Hole Location Figure 23 Post Back Hole Location ...
Page 50: ...50 Figure 24 Post Corner Hole Piping Figure 25 Post Back Hole Piping ...
Page 67: ...67 Gas Heater Instructions Figure 27 Gas Heater Instructions ...
Page 97: ......
Page 98: ......
Page 99: ......