55
LED Flash Alarm Codes
The flashing red LED will be to the right of
the screen. The number of blinks is
described below. The LCD screen will also
display the screens.
1
= LATA probe open/short
2
= LATB probe open/short
3
= OAT sensor open/short
4
= Leaving air temp over limit
5
= Cooling down after hi limit’ event
6
= LAT below low limit
7
= Stage 1 only recovery after
mechanical limit
8
= Shutdown after too many hi limit
events
9
= Short or overload on the 0-10VDC
analog signal output
Operation
Controller receives 24VAC preheat enable
Controller
evaluates
if
outside
air
temperature “OAT” is below setpoint
‘OATset’
If OAT < ‘OATset’, controller will delay
heating
startup
by
time
setpoint
‘STARTDLY’, then stage up preheat to
maintain the setpoint ‘LATset’ to a
maximum number of stages set in setpoint
‘Stages’.
If a safety is reached with the controller’s
safety sensors then the electric preheat will
be de-energized for a period of 2 minutes.
Electric preheat will turn on stage one at
100% for 3 minutes to test if fault conditions
still exist after the cool down period. The
controller will repeat this and if 3 trips are
recorded in 60 minutes then the controller
will lockout and require manually cycling
power to reset.
Summary of Contents for RQ SERIES
Page 2: ......
Page 29: ...29 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations ...
Page 43: ...43 Figure 21 Example 2 6 ton through the Base Gas Piping ...
Page 49: ...49 Figure 22 Post Corner Hole Location Figure 23 Post Back Hole Location ...
Page 50: ...50 Figure 24 Post Corner Hole Piping Figure 25 Post Back Hole Piping ...
Page 67: ...67 Gas Heater Instructions Figure 27 Gas Heater Instructions ...
Page 97: ......
Page 98: ......
Page 99: ......