58
at a time to provide slip fit clearance when
the wheel is rotated by hand.
Confirm that the wheel rotates freely. Apply
power to the unit and confirm rotation.
Airflow Balancing and Checking
High performance systems commonly have
complex air distribution and fan systems.
Unqualified personnel should not attempt to
adjust fan operation, or air circulation, as all
systems
have
unique
operations
characteristics. Professional air balance
specialists should be employed to establish
actual operating conditions, and to configure
the air delivery system for optimal
performance.
Controls
A variety of controls and electrical
accessories may be provided with the
equipment. Identify the controls on each unit
by consulting appropriate submittal, or order
documents, and operate according to the
control manufacturer’s instructions. If you
cannot locate installation, operation, or
maintenance information for the specific
controls,
then
contact
your
sales
representative, or the control manufacturer
for assistance.
Routine Maintenance and Handling
Handle cassettes with care. All cassettes
should be lifted by the bearing support
beam. Holes are provided on both sides of
the bearing support beams to facilitate
rigging
as
shown
in
the
following
illustration.
Routine
maintenance
of
the
Energy
Recovery
Cassettes
includes
periodic
cleaning of the Energy Recovery Wheel as
well as inspection of the Air Seals and
Wheel Drive Components as follows:
Lifting Hole Locations
Cleaning
The need for periodic cleaning of the energy
recovery wheel will be a function of
operating
schedule,
climate
and
contaminants in the indoor air being
exhausted and the outdoor air being supplied
to the building.
The energy recovery wheel is “self-
cleaning” with respect to dry particles due to
its laminar flow characteristics. Smaller
particles pass through; larger particles land
on the surface and are blown clear as the
flow direction is reversed. Any material that
builds up on the face of the wheel can be
removed with a brush or vacuum. The
primary need for cleaning is to remove oil
based aerosols that have condensed on
energy transfer surfaces.
Do not alter factory wiring. Deviation
from the supplied wiring diagram will
void all warranties, and may result in
equipment
damage
or
personal
injury. Contact the factory with wiring
discrepancies.
WARNING
Summary of Contents for RQ SERIES
Page 2: ......
Page 29: ...29 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations ...
Page 43: ...43 Figure 21 Example 2 6 ton through the Base Gas Piping ...
Page 49: ...49 Figure 22 Post Corner Hole Location Figure 23 Post Back Hole Location ...
Page 50: ...50 Figure 24 Post Corner Hole Piping Figure 25 Post Back Hole Piping ...
Page 67: ...67 Gas Heater Instructions Figure 27 Gas Heater Instructions ...
Page 97: ......
Page 98: ......
Page 99: ......