Note:
Low Ambient Operation
Air-cooled DX units without a low ambient
option, such as condenser fan cycling, ECM
driven condenser fans or the 0°F low
ambient option, will not operate in the
cooling mode of operation properly when
the outdoor temperature is below 55°F. Low
ambient and/or economizer options are
recommended if cooling operation below
55°F is expected.
Note:
Multiple
Units
with
Multiple
Thermostats
When several heating and cooling units are
used to condition a space all unit thermostat
switches must be set in either heating mode,
cooling mode or off. Do not leave part of the
units switched to the opposite mode.
Cooling only units should be switched off at
the thermostat during the heating season.
Gas or Electric Heating
The unit is designed to heat a given amount
of air while operating. If this amount of air
is greatly reduced, approximately 1/3 during
the heating season, the gas heat exchanger or
electric heating coil may overheat, and may
cut the burner or heater off entirely by action
of the safety high temperature limit devices
which are factory mounted at the heat
exchanger and supply fan areas.
Airflow should be adjusted after installation
to obtain an air temperature rise within the
range specified on the unit rating plate at the
required external static pressure.
Should overheating occur with a gas heat
exchanger, or the gas supply fail to shut off,
shut off the manual gas valve to the furnace
before shutting off the electrical supply.
Prolonged overheating of the heat exchanger
will shorten its life.
If unit has not been selected as a 100%
outside air unit (makeup air unit) the return
air duct must be sealed to the unit and the
return air temperature must be maintained
between 55
F and 80
F.
Table 1 - Electric and Gas Heating Capacities
Model
Option B2
Gas Heat
Electric Heat
Input Capacity
Output Capacity
Capacity
MBH
MBH
kW (208V)
kW (230V, 380V ,
460V, 575V)
1
=
Heat 1
60.0
48.6
7.5
10
2
=
Heat 2
15.0
20
3
=
Heat 3
100.0
81.0
22.5
30
4
=
Heat 4
30.0
40
5
=
Heat 5
140.0
113.4
6
=
Heat 6
7
=
Heat 7
160.0
129.6
Summary of Contents for RQ SERIES
Page 2: ......
Page 29: ...29 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations ...
Page 43: ...43 Figure 21 Example 2 6 ton through the Base Gas Piping ...
Page 49: ...49 Figure 22 Post Corner Hole Location Figure 23 Post Back Hole Location ...
Page 50: ...50 Figure 24 Post Corner Hole Piping Figure 25 Post Back Hole Piping ...
Page 67: ...67 Gas Heater Instructions Figure 27 Gas Heater Instructions ...
Page 97: ......
Page 98: ......
Page 99: ......