Circuit Breaker Sizing
Maximum circuit lengths for various circuit breaker amperages are shown below. Circuit breaker sizing should be based
on the local or applicable code.
Ground fault protection equipment is required for each branch circuit supplying electrical heating equipment. Consult
local authority for ground fault circuit protection.
Certifications/Approvals
Canadian Standards Association
Ordinary (Non-Classified) Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups F and G
Meets or exceeds - IEEE 515, 515.1 – UL 1588
CSA 130-16
Maximum Circuit Length vs. Breaker Size – 240 Vac
Service Voltage feet (meters)
Maximum Circuit Length vs. Breaker Size – 120 Vac
Service Voltage feet (meters)
TTS 5-1
TTS 8-1
TTS
10-1
Circuit Breaker Size
Cable
Type
Start-Up
Temp.
30 A
20 A
15 A
°C (°F)
40 A
10 (50)
-18 (0)
-29 (-20)
-40 (-40)
180 (55)
155 (47)
140 (43)
125 (38)
240 (73)
205 (62)
185 (56)
165 (50)
285 (87)
285 (87)
275 (84)
250 (76)
285 (87)
285 (87)
285 (87)
265 (81)
10 (50)
-18 (0)
-29 (-20)
-40 (-40)
145 (44)
115 (35)
100 (31)
90 (27)
195 (59)
150 (46)
135 (41)
120 (37)
240 (73)
225 (69)
200 (61)
180 (55)
240 (73)
240 (73)
240 (73)
215 (66)
10 (50)
-18 (0)
-29 (-20)
-40 (-40)
120 (37)
85 (26)
75 (23)
70 (21)
160 (49)
115 (35)
100 (30)
90 (27)
200 (61)
170 (52)
150 (46)
135 (41)
200 (61)
200 (61)
200 (61)
180 (56)
TTS Cable
5-2
TTS 8-2
TTS
10-2
Circuit Breaker Size
Cable
Type
Start-Up
Temp.
30 A
20 A
15 A
°C (°F)
40 A
10 (50)
-18 (0)
-29 (-20)
-40 (-40)
365 (111)
295 (90)
260 (79)
240 (73)
485 (148)
395 (120)
350 (107)
315 (96)
385 (117)
285 (87)
255 (78)
230 (70)
585 (178)
585 (178)
525 (160)
475 (145)
585 (178)
585 (178)
585 (178)
535 (163)
10 (50)
-18 (0)
-29 (-20)
-40 (-40)
290 (88)
215 (66)
190 (58)
170 (52)
485 (148)
430 (131)
380 (116)
345 (105)
485 (148)
485 (148)
480 (147)
480 (147)
10 (50)
-18 (0)
-29 (-20)
-40 (-40)
240 (73)
170 (52)
150 (46)
135 (41)
320 (98)
225 (69)
200 (61)
180 (55)
405 (123)
340 (104)
305 (93)
275 (84)
405 (123)
405 (123)
405 (123)
365 (111)
Table 1.3.2
Table 1.3.3