Average Velocity V1 (pre-cut) for a
given taping head is too low
(i.e. < 11)
Troubleshooting Guide
1. Box is slipping as it travels
through the machine.
Check the box height or width
adjustment to prevent box to belt
slippage
2. Dancer arm roller is not turning
2A. Check to insure dancer arm
assembly is in proper position and
providing adequate force against the
tape supply roll.
2B. Check to insure knurled surface of
dancer arm roller is clean and not worn.
2C. Check roller shaft and roller inner
diameter for problems.
2D. Check to insure tape dispense
proximity sensor is not located too far
in and contacting roller.
3. Tape dispense proximity sensor
is too far from roller “targets”.
Loosen and move head of proximity
sensor within 1mm (.040”) of back
of roller to sense targets.
4. Setup parameter timer TH051
is not set to the proper value.
Set to correct value. Value should
be set to the amount of time it takes
the leading edge of the box to travel
from the box present sensor to within
½” of the end of the cuto
ff
bracket
for lower taping head. If only the up-
per taping head is monitored adjust
to within ½” of the upper head’s end
of cuto
ff
bracket.
Average Velocity V2 (post-cut) for a
given taping head is too high (i.e. > 4)
Sampling time T053 is set too low.
Check timer. Typically this value is
set between 80 – 100. Note:
Higher
values delay when the case sealer will
be shut o
ff
in the advent of a fault,
thus allowing the box to escape the
machine before shutdown.
Problem
Cause
or case sealer continuously shuts
down with a tape did not apply
error. (i.e. HMI displays "User 101"
or "User 201"
Troubleshooting
The tape application monitoring
system doesn’t
generate a fault and
shut down the case sealer when the
tape does not cut.
1. There is no gravity or powered
out-feed conveyor at the exit end
of the case sealer.
If the newly sealed box is allowed to
stop at the exit end of the case sealer
this can appear as a normal tape cut
(i.e. V2 << V1). Add a conveyor to
remove the box.
2. Sampling time T053 is set too low. Check timer. Typically this value is
set between 80 – 100. Note:
Higher
values delay when the case sealer
will be shut o
ff
in the advent of a
fault, thus allowing the box to es-
cape the machine before shutdown.