North American - ENG
Date Released:
05-22-18
TAM Application Monitor - Yype 21800
Page 17
44-0009-2048-6 / ECO# 0078483
Setting the PLC Application Parameters
A remote HMI display mounted to the junction box cover is used to set the
operational parameters and provide the necessary fault screens.
Note:
For application speci
fi
c data register and timer values refer to the
Adjustments Section of this manual
.
Parameter Setup thru HMI:
Following the Installation and Setup-Up instructions contained in this manual
power up the TAM control box by pressing the rocker switch (located on the
junction box) to the ON position and verify the screen shown is displayed on
the HMI unit
(Figure 2-18)
.
Press the “SYS CONFIG” Page to display the HMI display shown in
(Figure 2-19)
.
Starting with the taping heads to monitor press the lower left button to set the following:
31: Monitor ONLY LOWER Taping Head
32: Monitor ONLY UPPER Taping Head
33: Monitor BOTH Taping Heads (FACTORY SETTING)
Press the second button (i.e. Lower Right) to enable or bypass tape monitoring as follows:
0: ON Monitor (FACTORY SETTING)
1: OFF Monitor By-Pass
When completed, press the “PAGE EXIT” to return to the main menu.
Installation and Set-Up
(continued)
TAPE APPLICATION MONITORING
TYPE 21800
Software Version
SYS CONFIG
MONITOR
TAPING HEADS
ONLY LOWER (31)
ONLY UPPER (32)
BOTH (33)
MONITOR
ON (0)
OFF (1)
PAGE
EXIT
MONITOR
VELOCITIES
PARAMETER
TIMERS
PARAMETER
OTHER
2
Figure 2-18
Figure 2-19
33
0