ZXG10 iBSC Hardware Installation Guide
Figure 10-2 Connection and Fixation between Power Cable and Grounding Cable (2)
1.
Copper bar
2.
Plain washer
3.
Nut
4.
Bolt
5.
Terminal
6.
Spring washer
10.2.2 Checking Power Cable Cabling
The method to route power cable is explained as follows.
1.
To connect the power cables or grounding cables to the connection terminals, use
the pliers to shape the cables for cabling. The cabling should be flat and straight
and the bindings are orderly. During the cabling process, the cable connected to the
connection terminal that is farther from the cabling end should be deployed at the outer
side, and the cable connected to the connection terminal that nearer the cabling end
should be deployed at the inner side.
2.
Intra-rack cables or the cables in cabling troughs or ditches should be bound separately
and not mixed with others. The power cables and grounding cables should pass
through the cabling chutes at the both sides of the cabinet. The cable ties should
be located on the external side of the chute.