Chapter 8 Installing the Alarm System
Table 8-1 Relation Between the Cable Ports and Sensors at End B
End B ID
Sensor
B1
Equipment room access control sensor
B2
Infrared Sensor
B3
Temperature/humidity sensor
B4
Smog sensor
B5
Reserved
When installing the cabinet, configure the sensors as required.
8.2.1 Installing Smog Sensor
Context
The smog sensor cable contains the sensor, its cable structure as shown in
Figure 8-3 Smog sensor cable
Steps
1.
Confirm the installation location of smog sensor.
The smog sensor is mounted on the ceiling, right over the top of the cabinet.
2.
Connect DB9 connector of End A to End B4 of the external monitoring cable
H-MON-009 on PWRDB.
– End of Steps –
8-3
SJ-20110531095035-004|2011-10-28 (R2.0)
ZTE Proprietary and Confidential