  1.   Electrical wiring and protection must be in accordance with National   

  Electrical Code and any other applicable state and local electrical   

 requirements.

  2.   All installations require a basin cover to prevent debris from falling into 

the basin and to prevent accidental injury.

  3.   Securely tape or clamp power cord to discharge pipe, clear of the float 

mechanism(s).

  4.  Use full-size discharge pipe.

  5.   Basin must be in accordance with applicable codes and specifications.

  6.   Pump must be level and float mechanism(s) clear of sides of basin 

before starting pump.  Float switch may be repositioned as needed.

  7.  Basin must be clean and free of debris after installation.

  8.   Gate valve or ball valve to be supplied by installer and installed 

according to any and all codes.

  9.  Gas tight seals required to contain gases and odors.

  10.   Vent gases and odors to the atmosphere through vent pipe.

  11.    Install Zoeller Pump Stand (Model 10-2421) under pump to  

  provide space for settling dirt, sand, or grit".

RECOMMENDED INSTALLATION FOR ALL APPLICATIONS

EASY DO'S & DON'TS FOR INSTALLING A SUMP PUMP

   1.  DO read thoroughly all installation material provided with the system.

   2.  DO inspect system for any visible damage caused by shipping.  Contact 

dealer if system appears to be damaged.

   3.  DO clean all debris from the sump.  Be sure that the pump will have 

a hard, flat surface beneath it.  DO NOT install on sand, gravel or dirt.

   4.  DO be sure that the sump is large enough to allow proper clearance 

for the level control switch(es) to operate properly.

   5.  DO always disconnect pump from power source before handling.

  6.  DO always connect to a separately protected and properly grounded 

circuit.

  7.  DO NOT ever cut, splice, or damage power cord (only splice in a 

watertight junction box).

  8.  DO NOT carry or lift pump by its power cord.

  9.  DO NOT use an extension cord with a sump pump.

  10.  DO  install a union in the discharge line.

  11.  DO  NOT use a discharge pipe smaller than the pump discharge.

  12.  DO  NOT use a sump pump as a trench or excavation pump, or for 

pumping sewage, gasoline, or other hazardous liquids.

 13.  DO  test system immediately after installation to be sure that the 

system is working properly.

  14.  DO  cover sump with an adequate sump cover.

  15.  DO  review all applicable local and national codes and verify that the 

installation conforms to each of them.

  16.  DO  consult manufacturer for clarifications or questions.

  17.  DO  inspect and test system for proper operations at least every three 

months.

as necessary. 

  8.  Install the Fit Controller (see Figure 3) by using the anchors provided.  

For  best  cooling,  install  wall  mount  configuration.  The  controller 

should be located at least 3' (1 m) above the sump.

  9.  Connect the leads from the controller to the battery terminals.  

Positive  (+)  lead  to  positive  terminal  and  black  neg.  (-)  lead  to 

negative battery terminal.  

  

CAUTION

Correct battery hook-up is essential for operation 

of the system. Use wing nuts supplied with battery and eyelet 

connectors  on  battery  wire  leads.  The  positive  terminal  is  the 

larger  stud,  3/8"  (10  mm)  diameter.  The  smaller  stud,  5/16"  (8 

mm)  diameter  is  the  negative  terminal.  The  stud  sizes  on  some 

batteries  may  be  identical.  Apply  grease  to  the  terminals  to  help 

prevent corrosion. Tighten slightly past finger tight with a wrench. 

 

Always  use  extreme  caution  around  batteries.  Be  careful  not  to 

“cross” or “short across” the battery terminals with your wrench or 

any other metal object.

 10.  Connect the DC pump's plug into the controller terminal. 

 11.  Plug the controller into the 115 V wall outlet. The primary sump pump 

and the controller should be on separate circuits.

 12.  Reconnect power to the primary sump pump.

 13.  The Aquanot

®

 Fit Controller is designed for use with Z Control

®

.

  1.  The preferred method of installation for backup pumps is shown in Figure 1. 

 

The installation kit includes the parts needed to install as in Figure 1. A 

check valve is incorporated in the discharge of the backup pump.

    NOTE: Do not install in small spaces where the controller will not be 

properly cooled. Do not operate in > 80 

º

F environment.

  2.  Remove all parts from the shipping carton, and make sure all parts are 

included. Refer to the parts list on page 3.

  3.  Select a location for the battery and the controller. The controller must 

be within 8' (2.4 m) of a 115 V wall outlet and within 6' (1.8 m) of pump and 

basin. Connect to a separate electrical circuit from the primary pump.

  4.  If the primary pump is installed, disconnect power.

    NOTE: Discharge piping must be 1-1/2" SCH 40 PVC
  5.  Ensure the O-ring is properly located on the pump discharge. Slide the 

DC  pump  into  the  fitting,  and  tighten  the  hose  clamp.  Soapy  water  is 

recommended as a lubricant.

    NOTE: The pump must be pushed all the way into the fitting to prevent 

the fitting from leaking. Place the clamp at the edge of the fitting so that 

the slotted sections can sufficiently tighten around the pump discharge. 

(see Figure 2) 

  6.  Measure, cut and solvent weld any remaining discharge piping above 

the tee. 

  7.  Check pre-set float operations to ensure the hose clamp screws will not 

interfere with the float operation of the primary pump. The float switch 

can be moved on the discharge pipe, or the rubber stops can be adjusted 

INSTALLATION

Содержание ProPak AQUANOT FIT 508/63

Страница 1: ...5 V outlet DO NOT USE AN EXTENSION CORD 2 Make sure the 115 V electrical supply circuit is equipped with fuses or circuit breakers of proper capacity 3 DC emergency pumps are designed for handling cle...

Страница 2: ...state Discharge Feet of Head 5 1 5 m 10 3 m 15 4 6 m 28 85 m Flow GPM LPM 12 7 volts 43 163 35 132 27 102 Shut off Head This system is a combination of a primary sump pump and a backup pump to your pr...

Страница 3: ...Install the Fit Controller see Figure 3 by using the anchors provided For best cooling install wall mount configuration The controller should be located at least 3 1 m above the sump 9 Connect the lea...

Страница 4: ...controllerwillturnthepumponand off a few times before running the pump continuously This is to purge a suspected air lock If the high water float is removed unplugged the resulting controller and pump...

Страница 5: ...DC PUMP INSTALLED IN LINE WITH SUBMERSIBLE PUMP BATTERY BOX AQUANOT FIT CONTROLLER OUTLET CONTROLLER HI WATER REED SENSOR 1 1 2 SCH 40 PVC PIPE X 10 254 mm LG 1 1 2 SCH 40 PVC TEE NOTE CHECK VALVE SC...

Страница 6: ...oller 1 155368 9 Fuse 30 amp automotive blade type 1 016918 10 High water float N C 1 155653 11 Battery box asm box and cover 1 10 0764 12 Hardware pak charger switch mode 2 152864 13 Pump M53 115V 1...

Страница 7: ...ed Z Control Connected Searching Broadcasting SSID or Dormant Note will not persist if pump didn t pump water See also the laminated label affixed to the controller s cord This cord label also describ...

Страница 8: ...oints Clean if required c Check for low battery Service battery if required d Check 30 amp fuse on controller see fig 3 If fuse is blown replace with 30 amp automotive blade fuse e Remove pump Check f...

Страница 9: ...rol Cloud will also be updated with the firmware update information and notification to email accounts will occur 5 You now should go back to the Z Control app to find your new device set up in the lo...

Страница 10: ...ection to router is not successful If you need to force the Fit into AP mode again press the Z Control button for 12 seconds See Figure A This will cause the Fit to re enter AP mode and begin transmit...

Страница 11: ...ng installed After up to 1 minute the Fit will restart and return to normal operation The Fit s alert history on the Z Control Cloud will also be updated with the firmware upgrade information and nofi...

Страница 12: ...s by products capable of causing the CO detector to activate Contact the manufacturer and ask for recommendations to prevent the alarm activation There are millions of batteries manufactured each year...

Отзывы: