FIT CONTROLLER FUNCTIONS
There are two buttons on the front of the controller.
- Silence/Reset
• Can be pressed to silence current alarms for 24 hours.
•
Can be held for 3+ seconds to reset (or clear) alarms and LEDs. Flashing LEDs for conditions such as bad/disconnected battery or
power outage, for example, can’t be cleared by Silence/Reset. These conditions must be remedied to eliminate the LED indicator.
- Test
• Will run the pump to determine if amp draw of pump is within range.
•
Controller is factory programmed to self-test the pump for several seconds every 24 hours. This schedule may be modified once the
Fit is connected to the Z Control Cloud.
• Pressing the test button will start the 24-hour timer for self-testing.
- Test and Silence/Reset
•
Holding both buttons together for about 6 seconds will initiate a Factory Reset. This returns the firmware’s device configuration to
the state in which it left the factory. Any over the air firmware updates that have been installed will be retained.
Solid
Flashing
Off
System Ready
No Faults (Green)
AC off with No Faults
(Green)
--
Battery
Charged (Green)
Low Battery (Red)
No AC Power
Charging (Yellow)
Bad Battery (Red)
DC pump
Pump Ran
(Yellow)*
Pump Running (Yellow)
--
Pump Fault (Red)
Float Status
High Water (Red)
Float Fault (Red)
--
Z Control
Connected
Searching
Broadcasting SSID or Dormant
* Note: will not persist if pump didn’t pump water.
See also the laminated label affixed to the controller’s cord. This cord label also describes LED and
button functionality.
The LEDs will display information about the controller.
AQUANOT FIT
MAINTENANCE
1. Inspect and test the system for proper operations at least every 3
months.*
(a) Green "system ready" indicator light should be on, indicating AC
power is on and there are no alarm conditions.
(b) Unplug the primary pump and the controller from the power supply.
(c) Fill the sump with water to the “on” level for the DC pump. Allow
the pump to run a few minutes.
(d) The alarm will sound approximately 1 second after the pump
starts
to run.
(e) Push the Silence/Reset button. The alarm will turn off.
(f) The pump will shut off after the water level is lowered and the
operational float drops
to the "off" position.
(g) Hold Silence/Reset button for 3 seconds to reset the controller
and clear any alarms or indicators.
2. Plug the controller and the primary pump into the wall outlet.
(a) The primary pump will come on, lower the water to the
normal
operating level and shut off.
(b) The battery light will be yellow when charging. The charger is
replacing
the energy consumed during the test. The green light
will come on after the charger has replaced the energy consumed
during the test.
*Electrolyte levels in wet cell batteries should be checked monthly. Such a
check is not required for "maintenance free" battery types.