8
ZP1-X3 Operation Manual
Item
Control/LED
LED colour Description
20
Fire Sounders
Start/Stop button
and LED
Red
The LED indicates what happens when the button
is pressed:
If the LED is on (flashing or steady), pressing the
button silences the fire sounders.
If the LED is off, pressing the button activates the
fire sounders (if the control panel status and
operating mode allow manual activation of
sounders).
The LED also indicates the status of the
sounders:
• Steady indicates that fire sounders are active
(or will be activated shortly)
• Flashing indicates that a delay countdown is
in progress (fire sounders are activated when
the configured delay elapses or when the
delay is cancelled)
• Off indicates that the fire sounders are off (or
will be deactivated shortly)
Note:
To prevent the immediate silencing of fire
sounders when an alarm is first reported, the Fire
Sounders Start/Stop button may be temporarily
disabled during a configured fire sounder delay
countdown. For more information, see “Stopping
or restarting fire sounders” on page 19.
21
Numeric keypad and
Enter button
N/A
Used to enter the operator level password.
The Enter button is also used to disable or test
selected features (when pressed with the General
Disable or Test button).
22
Manual Mode button
and LED
Yellow
Used to change from manual-only mode to
manual-automatic mode and vice versa, if
configured.
A steady yellow LED indicates that the control
panel is in manual only mode: the automatic fire
detection zones cannot generate the
extinguishing event.
Your system installer may have disabled this
feature by configuring an external device that is
connected to a control panel input.
23
System Fault LED
Yellow
Indicates a control panel processor failure.
24
Out of Service LED Yellow
Indicates that control panel power supply
conditions have put fire detection zones and
inputs out of service.
Other system functions remain operational.
A steady yellow LED indicates that there is no
mains power and the battery power is insufficient.
A flashing yellow LED indicates that the mains
power is insufficient and there is no battery
power.