10
ZP1-X3 Operation Manual
Item
Control/LED
LED colour Description
31
Fire Routing On
button and LEDs
Red/Yellow Overrides the configured delay (when this is
running) and activates fire routing. Disables or
tests fire routing (when pressed with the General
Disable or General Test button).
A flashing red LED indicates that fire routing is
activated.
A flashing yellow LED indicates a wiring fault. A
steady yellow LED indicates a disablement or a
test.
Consult your system installer to determine
whether the Fire routing option is configured.
Audible indicators
The control panel buzzer acts as an audible indicator to highlight system events.
It can sound a constant tone or an intermittent tone.
A constant tone can indicate a fire alarm, an extinguishing preactivation or
activation, an extinguishing released state, or a system fault.
An intermittent tone can indicate that:
• The control panel is in a fault condition.
• The control panel is in the last 10 seconds of a delay countdown before
activating the extinguishing actuator (extinguishing release is imminent).
Control panel status indications
This section includes a summary of the default control panel status indications.
Standby
Standby, or normal status, is indicated as follows:
• A steady Supply LED
• A steady Fire Sounders Delay LED (if a delay is enabled)
• A steady Fire Routing Delay LED (Figure 1, item 30) (if a delay is enabled)
There is no audible indication.
Fire alarm (fire-only)
The fire alarm state applies to zones that are not linked to the extinguishing area,
and act as fire-only zones.
A fire alarm in a detection zone that is not linked to the extinguishing area is
indicated as follows:
• General Fire Alarm LEDs: Flashing if the alarm was activated by a detector.
Steady if the alarm was activated by a manual call point.