18
ZP1-X3 Operation Manual
Acknowledging a system event and silencing the control panel buzzer
To acknowledge a system event and silence the control panel buzzer, press the
Panel Silence button.
A steady Panel Silence LED indicates that the control panel buzzer is silenced
and that all current events are acknowledged.
Cancelling an active fire sounders delay
If a fire sounders delay is enabled and active, press the Fire Sounder Delay
button to cancel the delay and activate the sounders immediately.
The Fire Sounders Delay LED indicates the following conditions:
• Steady: A delay is configured and enabled.
• Flashing (during a fire alarm): A countdown for the configured delay is in
progress. Sounders activate when the delay elapses or when the delay is
cancelled.
Note:
If an alarm is reported in a zone linked to the extinguishing event, any
configured delay is ignored and the fire sounders are activated immediately.
A fire alarm activated by a manual call point overrides any configured delay and
activates the fire sounders immediately.
Cancelling an active fire routing delay
If a fire routing delay is enabled and active, press the Fire Routing On button or
the Fire Routing Delay button to cancel the delay and activate fire routing
immediately.
The Fire Routing Delay LED indicates the following conditions:
• Steady: A delay is configured and enabled.
• Flashing (during a fire alarm): A countdown for the configured delay is in
progress. Fire routing activates when the delay elapses or when the delay is
cancelled.
A fire alarm activated by a manual call point overrides any configured delay and
activates fire routing immediately.
Performing a control panel LED indicator and buzzer test
To perform a control panel LED indicator and buzzer test, press and hold the
Test button for more than 3 seconds.
The test is indicated as follows:
• All LEDs are steady.
• The control panel buzzer sounds continuously.
The test continues for as long as the Test button remains pressed (with an
automatic timeout of 12 seconds). When the test is completed the control panel
returns to its former state.