ZP1-X3 Operation Manual 

25 

To test any of these devices, press the General Test button for more than 3 

seconds, press the 1 and 3 buttons (the Up and Down buttons) to select the 

option to be tested (the corresponding LED flashes), and then press Enter to 

confirm the test condition. 
The test condition is indicated by: 
•  A steady General Test LED 
•  A steady test LED for the corresponding device 
To exit from a test condition, press the General Test button for more than 3 

seconds, press the 1 and 3 buttons to select the option, and then press Enter. 

Table 4: Additional input device test options 
Input device 

LED used 

Test functionality 

Pressure switch 

monitoring 

Low Pressure yellow 

A flashing Low Pressure LED indicates that the 

input has been activated. 

Extinguishing agent flow 

monitoring 

Extinguishing Agent 

Flow yellow 

A steady Extinguishing Agent Flow LED 

indicates that the input is active. 

Start extinguishing 

manual call point 

MCP Start yellow 

A steady MCP Start LED indicates that the 

input has been activated. 

Hold extinguishing 

manual call point 

MCP Hold yellow 

A steady MCP Hold LED indicates that the input 

has been activated. 

Abort extinguishing 

manual call point 

MCP Abort yellow 

A steady MCP Hold LED indicates that the input 

has been activated. 

 

The activation of any input under test will not activate any associated 

functionality. 

Table 5: Additional output device test options 
Output device 

LED used 

Test functionality 

Actuator 

Released yellow 

The actuator output will be 3 seconds on, 5 

seconds off, for the duration of the test. 
A steady Released LED indicates that the 

output is activated. 

Extinguishing release 

optical warning panel 

or sign 

Optical Panel On 

yellow 

The optical panel output will be 3 seconds on, 5 

seconds off, for the duration of the test. 
A steady Optical Panel On LED indicates that 

the output is activated. 

 

WARNING: 

Risk of death or serious injury. Disconnect the extinguishing agent 

actuator from the control panel 

before 

you issue the actuator output test 

command. When you confirm the test command, the actuator output is activated 

immediately. 

Содержание ZP1-X3

Страница 1: ...ZP1 X3 Operation Manual P N 501 419203 2 11 REV 01 10 ISS 12NOV13...

Страница 2: ...directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of...

Страница 3: ...ii Introduction 1 Control panel overview 3 The user interface 3 Operator controls and indicators 4 Audible indicators 10 Control panel status indications 10 Control panel operation 17 User levels 17 P...

Страница 4: ...lost profits or business opportunities loss of use business interruption loss of data or any other indirect special incidental or consequential damages under any theory of liability whether based in...

Страница 5: ...n this state fire sounders are activated immediately with a steady tone Fire routing if available is activated after any configured delay If an alarm is not reported in the second zone linked to the e...

Страница 6: ...tivated Normally your system installer will have configured the extinguishing sounders to change to a continuous tone The extinguishing process cannot be stopped once it has started and extinguishing...

Страница 7: ...tical Panel On LEDs 10 Door Fault Disabled LED 11 Networking Fault LED 12 Reserved for future use 13 Expansion I O Fault Disabled LED 14 General Disable button and LED 15 General Test button and LED 1...

Страница 8: ...ablement or a test 2 Supply LED Green Indicates that the system is powered up 3 General Fault LED Yellow Indicates a fault The corresponding zone device or function fault LED also activates 4 General...

Страница 9: ...ishing sounders are active sounding A flashing yellow LED indicates a wiring fault on the extinguishing sounders or if configured sounder outputs in expansion modules linked to the activation or relea...

Страница 10: ...vating the actuator to ensure property protection A steady LED indicates a disablement Consult your system installer to determine whether your system has this option configured 11 Networking Fault LED...

Страница 11: ...teady yellow LED indicates a disablement or test 17 Extinguishing Agent Flow LEDs Red Yellow Indicates the extinguishing agent flow status A steady red LED indicates that the extinguishing agent was r...

Страница 12: ...lay countdown For more information see Stopping or restarting fire sounders on page 19 21 Numeric keypad and Enter button N A Used to enter the operator level password The Enter button is also used to...

Страница 13: ...anual call point is active and the extinguishing process is paused A flashing yellow LED indicates an open or short circuit wiring fault A steady yellow LED indicates a disablement or test An MCP Hold...

Страница 14: ...inguishing released state or a system fault An intermittent tone can indicate that The control panel is in a fault condition The control panel is in the last 10 seconds of a delay countdown before act...

Страница 15: ...ED flashes Consult your system installer or maintenance contractor to determine whether your system has a zone configured for fire only operation The control panel buzzer sounds continuously Extinguis...

Страница 16: ...he device that prevented the event Extinguishing activation The extinguishing activation state is also called in delay to release The control panel is in this state when In automatic mode the extingui...

Страница 17: ...en the MCP Hold is activated the actuator delay countdown continues but the panel is prevented from entering the extinguishing activation state When the MCP Hold is deactivated the delay countdown det...

Страница 18: ...ate that manual reset is disabled until the configured delay expires Fire alarm indications will be on as usual if the extinguishing event that caused the release was not a start manual call point act...

Страница 19: ...rt extinguishing manual call points are indicated by a steady General Disable LED and a steady yellow LED for MCP Start MCP Hold or MCP Abort There is no audible indication Note Some disablements can...

Страница 20: ...ones and no activation deactivaton or fault signals from input devices are processed The out of service state is indicated as follows Out of Service LED Steady indicates that there is no mains power a...

Страница 21: ...d security To enter the operator user level enter the password using the numeric keypad and then press Enter A long beep and a steady Reset LED indicate that the correct password was entered and that...

Страница 22: ...by a manual call point overrides any configured delay and activates the fire sounders immediately Cancelling an active fire routing delay If a fire routing delay is enabled and active press the Fire...

Страница 23: ...inguishing event Disable other extinguishing devices Test other extinguishing devices Set the manual only mode of operation Resetting the control panel Note Investigate all alarms and system faults be...

Страница 24: ...Sounders Start Stop LED is flashing pressing the Fire Sounders Start Stop button will silence fire sounders before activation A configured fire sounder delay may still be cancelled while the delay is...

Страница 25: ...s Delay button Extinguishing sounder disablement is indicated as follows A steady General Disable LED A steady yellow LED for the Extinguishing Sounders On button To enable the fire sounders press the...

Страница 26: ...le a configured and enabled fire routing delay press the Fire Routing Delay button To enable the delay press the button again Testing fire routing Note Before performing any fire routing tests ensure...

Страница 27: ...e the control panel buzzer sounds continuously for 5 seconds see the note below The control panel resets automatically after 5 seconds and clears alarms for the zone in test To end the test press the...

Страница 28: ...steady General Disable LED A steady disabled LED for the corresponding device To enable a disabled option press the General Disable button for more than 3 seconds press the 1 and 3 buttons to select t...

Страница 29: ...yellow A steady MCP Start LED indicates that the input has been activated Hold extinguishing manual call point MCP Hold yellow A steady MCP Hold LED indicates that the input has been activated Abort...

Страница 30: ...al Mode LED In this mode the extinguishing event can only be generated by activation of the MCP Start point The fire detection zones in the extinguishing area cannot generate the extinguishing event P...

Страница 31: ...e system This inspection must test at least one device per zone and verify that the control panel responds to all fault and alarm events The control panel power supply and battery voltage should be ch...

Страница 32: ...54 2 clause 7 8 and should not be used for fire alarm devices 2 Requires installation of optional 2010 1 SB expansion board not supplied Table 7 EN 12094 1 optional requirements Option Description 4...

Страница 33: ...ion of Performance DoP Certification Certification body 0370 Manufacturer UTC CCS Manufacturing Polska Sp Z o o Ul Kolejowa 24 39 100 Ropczyce Poland Authorized EU manufacturing representative UTC Fir...

Страница 34: ...30 ZP1 X3 Operation Manual...

Страница 35: ......

Страница 36: ......

Отзывы: