21
The control panel may provide additional extinguishing sounders in expansion
modules linked to the preactivation or released state which activate continuously.
These outputs accept the stop and restart commands normally.
Disabling or enabling sounders
To disable the fire sounders, press the General Disable button, and then press
the Fire Sounders Delay button.
To disable the extinguishing sounders, press the General Disable button, and
then press the Extinguishing Sounders On button.
Sounders can only be disabled when the sounder outputs are not activated.
Disabled sounders do not operate or indicate a fault if there is an alarm.
Note:
Disabling the extinguishing sounders automatically prevents (disables) the
extinguishing event. See “Disabling or enabling the extinguishing event” on page
23 for more information.
Fire sounder disablement is indicated as follows:
• A steady General Disable LED
• A steady yellow LED for the Fire Sounders Delay button
Extinguishing sounder disablement is indicated as follows:
• A steady General Disable LED
• A steady yellow LED for the Extinguishing Sounders On button
To enable the fire sounders, press the General Disable button, and then press
the Fire Sounders Delay button again.
To enable the extinguishing sounders, press the General Disable button, and
then press the Extinguishing Sounders On button again.
Disabling or enabling a fire sounders delay
To disable a configured (and enabled) fire sounders delay, press the Fire
Sounders Delay button. To enable the delay, press the button again.
If an alarm is reported in a zone linked to the extinguishing event, any configured
delay will be ignored and fire sounders will be activated immediately.
Testing sounders
To test the sounders, press the General Test button, and then press the Fire
Sounders Delay button.
Sounders can only be tested when the control panel is in standby state.
The test is indicated as follows:
• A steady General Test LED
• A steady yellow LED for the Fire Sounders Delay button
• The audible sounder test signal (3 seconds on, 5 seconds off) for the duration
of the test, without any configured delay