22
ZP1-X3 Operation Manual
To end the test, press the General Test button, and then press the corresponding
sounder Fire Sounders Delay button again.
If there is an extinguishing preactivation, activation, release, or fire alarm event
during the test, the control panel exits the test and responds to the alarm event
as configured.
Disabling or enabling fire routing
To disable fire routing, press the General Disable button, and then press the Fire
Routing Start button.
The disablement is indicated as follows:
• A steady General Disable LED
• A steady yellow Fire Routing On LED
To enable fire routing, press the General Disable button, and then press the Fire
Routing On button again.
Note:
Disabled fire routing does not operate or indicate a fault if there is a fire
alarm.
Disabling or enabling a fire routing delay
To disable a configured (and enabled) fire routing delay, press the Fire Routing
Delay button. To enable the delay, press the button again.
Testing fire routing
Note:
Before performing any fire routing tests, ensure that the fire routing signals
are not connected or notify the fire brigade of the tests.
To test fire routing, press the General Test button, and then press the Fire
Routing Start button.
The test is indicated as follows:
• A steady General Test LED
• A steady yellow Fire Routing On LED
• A flashing Fire Routing On LED and the test signal (3 seconds on, 5 seconds
off) without any configured delay for the duration of the test
To end the test, press the General Test button, and then press the Fire Routing
On button again.
If there is an extinguishing preactivation, activation, release, or fire alarm event
during the test, the control panel exits the test and responds to the alarm event
as configured.
Disabling or enabling a zone
To disable a zone, press the General Disable button, and then press the
corresponding Zone button.
Содержание ZP1-X3
Страница 1: ...ZP1 X3 Operation Manual P N 501 419203 2 11 REV 01 10 ISS 12NOV13...
Страница 34: ...30 ZP1 X3 Operation Manual...
Страница 35: ......
Страница 36: ......