![Ziton ZP1-X3 Скачать руководство пользователя страница 18](http://html2.mh-extra.com/html/ziton/zp1-x3/zp1-x3_operation-manual_3844213018.webp)
14
ZP1-X3 Operation Manual
• The actuator output to release the extinguishing agent has been activated
and the agent flow has been confirmed, when agent flow confirmation is
configured.
Consult your system installer to determine the option configured in your system.
An extinguishing released state is indicated as follows:
• Released LED: Steady.
• Extinguishing Agent Flow LED: Steady, if confirmation is configured.
• Preactivation LED: Steady red, unless extinguishing agent flow confirmation
configured and received, but no extinguishing activation event occurred.
• General Fire Alarm LED: Steady. The Alarm relay activates.
• MCP Start LED: Steady if the alarm was activated by a start extinguishing
manual call point.
• Extinguishing Sounders On LED: Flashing (for intermittent tone) or steady (for
continuous tone) according to your system configuration.
• Optical Panel On LED: Steady to indicate that the output to activate the
optical warning panel or sign is active.
• Reset LED: Flashing slowly, to indicate that manual reset is disabled until the
configured delay expires.
Fire alarm indications will be on as usual if the extinguishing event that caused
the release was not a start manual call point activation. Fire routing indications, if
configured, are shown in the usual manner, linked to the fire alarm event.
The control panel buzzer sounds continuously.
Faults
Faults are indicated with a flashing General Fault LED and an active fault
indication LED corresponding to the feature or device with a fault.
The control panel buzzer sounds intermittently.
Note:
Contact your installation or maintenance contractor to solve all reported
faults. Some faults can prevent or disable the extinguishing event. See
“Extinguishing event prevented” on page 12 for more information.
Disablements
• A disabled extinguishing event is indicated by a steady General Disable LED
and a steady yellow Preactivation LED.
• Disabled zones are indicated by a steady General Disable LED and a steady
yellow Zone LED.
• Disabled extinguishing sounders (and sounder outputs linked to the
preactivation or released states) are indicated by a steady General Disable
LED and a steady yellow Extinguishing Sounders On LED.
Содержание ZP1-X3
Страница 1: ...ZP1 X3 Operation Manual P N 501 419203 2 11 REV 01 10 ISS 12NOV13...
Страница 34: ...30 ZP1 X3 Operation Manual...
Страница 35: ......
Страница 36: ......