Installation - Section 2 Ventilation
2.3 Preferred ventilation arrangements for commercial models
• The ducted vent kit supplied with the Command Centre exhausting through the kick-space should
be used, to provide adequate ventilation in all conditions. (Ancillary components are not shown in
these diagrams).
• The 100mm separation between inlet and outlet vents must be observed to prevent recirculation of
warm air back into the cupboard space.
2.2 Ventilation for all models
• The clearance envelope dimensions stated in the specification sheets and installation instructions
must be observed.
• Adequate ventilation must be provided to ensure that the cupboard space temperature does not
exceed 35
0
C.
B
A
C
100mm min.
Cupboard back must be
fully closed to prevent
recirculation into cupboard
from kick space.