Error code
Error
Possible cause
Measure
0x306
The configured "DeviceMode" is
implausible.
• Wrong value in the
"DeviceMode" parameter
►
Adjust the "DeviceMode"
►
Universal = 100
►
Grip workpiece outside = 60
►
Grip workpiece inside = 70
0x307
Movement order cannot be
executed.
• Multiple move commands in
the same direction
• Move command transmitted
despite existing error.
►
Reset the direction flag and
send the move command
again.
0x308
"WorkpieceNo" not available.
• Transmitted workpiece number
is outside the permitted range
0 to 32.
►
Check the values of the
"WorkpieceNo" parameter
►
Apply the process data via a
"Handshake."
0x309
"TeachPosition" not transferred. • Process data sent by the
master has been changed.
►
Confirm the newly transmitted
process data with a
"Handshake" "ControlWord" =
0x1.
0x30D
"GripForce" not transferred.
• Process data sent by the
master has been changed.
►
Confirm the newly transmitted
process data with a
"Handshake" "ControlWord" =
0x1.
0x30E
"DriveVelocity" not transferred.
• Process data sent by the
master has been changed.
►
Confirm the newly transmitted
process data with a
"Handshake" "ControlWord" =
0x1.
0x30F
"TeachTolerance" not trans-
ferred.
• Process data sent by the
master has been changed.
►
Confirm the newly transmitted
process data with a
"Handshake" "ControlWord" =
0x1.
0x310
"DeviceMode" not applied.
• Process data sent by the
master has been changed.
►
Confirm the newly transmitted
process data with a
"Handshake" "ControlWord" =
0x1.
0x311
Initial "Handshake" is missing.
• Process data sent by the
master has been changed.
►
Confirm the newly transmitted
process data with a
"Handshake" "ControlWord" =
0x1.
0x312
“WorkpieceNo." not available.
• After a cold boot, a one-time
data transfer via ControlWord =
1 must be carried out.
►
Confirm the current process
data with a "Handshake,"
ControlWord = 0x1.
0x314
"BasePosition" greater than
"WorkPosition"
• Transferred "BasePosition" is
greater than or equal to the
transferred "WorkPosition."
►
Check the transmitted process
data
0x400
Gripper is jammed.
•
Gripper is difficult to move.
• Travel path of the gripper is
impeded.
►
Restore the ease of movement
of the gripper.
►
Reset via "ControlWord" =
0x8000
0x406
System error
• Internal system error
►
Contact Zimmer Customer
Service.
0x40B
Gripper-internal parameters are
not consistent.
• Incompatible or damaged
parameters were loaded.
►
Contact Zimmer Customer
Service.