UFR1002IP
12690-0701-00
Seite
43 / 50
www.ziehl.de
Finland
Ireland
Netherlands France
SFS-EN50549-
1+2:2019
EN50549-1
2-stage
NEN-
EN50549-
1:2019
VDE
0126
VFR2019
My
3AC+N
3AC
3AC+N
3AC
3AC+N
3AC+N
Data
230 V
400 V
230 V
400 V
230 V
230 V
Main
Sub
Parameter
Pr1.30
Pr1.31
Pr1.32
Pr1.33
Pr1.34
Pr1.36
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ver. 00
U0
Alarm active
no
no
no
no
no
no
59v0
Alarm on
[V]
46,0
80,0
46,0
80,0
46,0
46,0
Alarm off
[V]
36,0
70,0
36,0
70,0
36,0
36,0
Delay alarm on [s]
1,50
1,50
1,50
1,50
1,50
1,50
Delay alarm off [s]
60
60
60
60
60
60
Display U0/UM> [s]
5,0
5,0
5,0
5,0
5,0
5,0
F
requ
ency
f >>
Alarm active
no
no
yes
yes
no
no
81.S2
Alarm on
[Hz]
51,50
51,50
52,10
52,10
51,50
51,50
81>S2
Alarm off
[Hz]
51,00
51,00
50,15
50,15
50,10
50,05
Delay alarm on [s]
0,20
0,20
0,50
0,50
0,10
0,10
Delay alarm off [s]
60
60
20
20
60
60
f >
Alarm active
yes
yes
no
no
yes
yes
81.S1
Alarm on
Hz
51,50
51,50
51,50
51,50
51,50
51,50
81>S1
Alarm off
Hz
51,00
51,00
50,05
50,05
50,10
50,05
Delay alarm on [s]
0,20
0,20
90,00
90,00
0,10
0,10
Delay alarm off [s]
60
60
20
20
60
60
f <
Alarm active
yes
yes
no
no
yes
yes
81.S1
Alarm on
[Hz]
47,50
47,50
47,50
47,50
47,50
47,50
81<S1
Alarm off
[Hz]
49,00
49,00
48,50
48,50
48,50
48,50
Delay alarm on [s]
0,20
0,20
20,00
20,00
0,10
0,10
Delay alarm off [s]
60
60
20
20
60
60
f <<
Alarm active
no
no
yes
yes
no
no
81.S2
Alarm on
[Hz]
47,50
47,50
46,90
46,90
47,50
47,50
81<S2
Alarm off
[Hz]
49,00
49,00
47,90
47,90
48,50
48,50
Delay alarm on [s]
0,20
0,20
0,50
0,50
0,10
0,10
Delay alarm off [s]
60
60
20
20
60
60
f/U< protect Alarm active
no
no
no
no
no
no
U< Limit
[V]
46,0
46,0
46,0
46,0
46,0
46,0
Frequency- Alarm active
range
Alarm U< on
[V]
Alarm U< off
[V]
Alarm 3U0 on
[V]
Alarm 3U0 off
[V]
Delay alarm on [s]
Delay alarm off [s]
V
ec
to
r
shif
t
Alarm active
no
no
no
no
no
no
VSR deg
°
10,0
10,0
50,0
50,0
10,0
10,0
Delay alarm off [s]
3
3
20
20
60
3
suppression
[s]
2
2
2
2
2
3
RO
CO
F
Alarm active
no
no
yes
yes
no
no
df / dt
2,000
2,000
1,000
1,000
0,800
0,800
Periods
20
20
20
20
20
20
Delay alarm on [s]
0,50
0,50
0,60
0,60
0,10
0,10
Delay alarm off [s]
60
60
20
20
60
60
F
ee
d
-
b
ac
k
Feedback at
off
off
off
off
off
off
Time for feedb. [s]
1,5
1,5
1,5
1,5
1,5
1,5
Reclosing
attempts
2
2
2
2
2
2
Reclosing Time [s]
5
5
5
5
5
5