Error search
In the event of a device error, an
Err
is displayed on the display pages and a
„
→
“
indicates an error page.
By pressing the joystick button to the right (
→)
, you can navigate to a fault description.
Error
Cause
Remedy
Measured value on the
display shows EEE / -EE
Measured value is too large or
too small
Check or remeasure the measured values.
Observe measuring ranges.
Error message on the
display:
Error: Feedback
Error on the feedback contacts
of the section switch (terminals
Y0, Y1, Y2). Incorrect or
implausible condition.
No feedback contacts connected:
Program feedback, select "off" in the menu
"Feedback" -> "Message on".
Feedback contact(s) connected:
- Check correct connection
- Check plausibility of parameters in the
"Feedback" menu ("Message to..." and
"Time for message").
-> Perform reset: Press the joystick button
≥ 2s upwards (
↑
).
Error message on the
display:
Error: Feedback off
Implausible state on the
feedback contacts or
shutdown time of the section
switch > 0.5 s.
(Terminals Y0, Y1, Y2).
Check feedback contacts on Y0-Y1 (Y0-
Y2).
Check the shutdown time(s) of the section
switch (s) -> in the menu "Test/Simulation"
-> "Test K1/K2"
Error message on the
display:
int. error slave 1
int. error slave 2
Error MA./slave 1
Error MA./slave 2
Error int. voltage
Internal device errors.
Switch the device off and on again
(interrupt control voltage Us for > 5 s).
Error in parameter alarm
Implausible alarm values are
programmed.
Check parameters for alarm on and alarm
off (all U and F alarms).
Internal memory error
Device internal memory error
Switch the device off and on again
(interrupt control voltage Us for > 5 s).
Invalid calibration values
Calibration error
Device is defective!
Parameter error
Invalid parameter
Switch the device off and on again
(interrupt control voltage Us for > 5 s).
Measurement tolerance
error >>
Measured value deviation in
the internal measuring
channels too high
Switch the device off and on again
(interrupt control voltage Us for > 5 s).
Firmware version error
Incorrect/incompatible
firmware versions installed
- Perform firmware update (only possible
via web interface)
- Reset firmware to delivery status -> 8.16
Firmware update