UFR1002IP
12690-0701-00
Seite
6 / 50
www.ziehl.de
Logging:
•
Alarm counter (resettable)
o
Memory for number of alarms (resettable)
o
Memory for 100 alarms (shutdowns)
o
Storage of trigger value, cause, time stamp of shutdown and time stamp of reconnection
o
Total alarm time (resettable)
•
Standby statistics (shutdowns via digital input E1/E2)
o
Memory for number of standby events (resettable)
o
Memory for 10 standby shutdowns
o
Storage of time stamp for shutdown and time stamp for reconnection
o
Total time for standby (resettable)
Ethernet interface:
•
integrated web server, for
o
Display of measured values
o
Display of operating states
o
Programming
o
Simulation
o
Display alarm counter and standby counter (with csv download)
o
Firmware Updates
o
Updates for programs (default settings)
o
saving and transferring device configurations
•
Modbus TCP (read)
Display and operation
•
colour LCD display for displaying the operating conditions and for programming
•
intuitive operations via joystick
•
convenient display of operating conditions
•
Programming via Ethernet interface on the PC (web browser) is possible
Other features:
•
Single fault safety
•
Monitoring of section switches (can be switched off when using the integrated section switches of PV
and battery inverters in accordance with DIN EN 62109 (VDE 0126-4))
•
Standby input
•
Restart attempts for power-
on error, number adjustable, 0…3
•
passive stand-alone network detection in accordance with Chapter 6.5.3 and Appendix D2
•
Test and simulation functions with measurement of shutdown times
•
Adjustable response times, 0.05…300.0 s
•
Adjustable reset times, 0…6000 s
•
Protection of device settings by sealing and code protection (values can still be read)
•
Integrated real-time clock (power reserve > 11 days at 25°C)
•
Connection of a Ziehl coupling device VG1200 for measuring max. 875 V (Ph-N) or 1500 V (Ph-Ph) is
possible
•
Change of the rated voltage during program setting -> voltage alarms are automatically adjusted
•
Control voltage AC/DC 24-270 V
•
Distribution box V6, 6 TE, 105 mm wide, installation depth 66 mm