8.8 Set program
Depending on the application, the appropriate program must be set on the UFR1002IP.
If the UFR1002IP is locked by sealing (red lock in the upper right display), it must be deactivated first.
Country Program
Connection
Rated voltage Standard
1.02
3 AC with N
230 V
VDE-AR-N 4105:2018
1.01
3 AC with N
230 V
VDE-AR-N 4105:2011
1.07
1 AC with N
230 V
1.08
3 AC with N
230 V
VDE-AR-
N 4105:2018, Generator Pn ≤ 50 kW
1.09
3 AC with N
230 V
VDE-AR-N 4105:2018, Generator Pn > 50 kW
1.03
3 AC with N
57,7 V
BDEW Juni 2008 nach 3.2.3.3-1
1.04
3 AC without N 100 V
1.05
3 AC with N
230 V
1.06
3 AC without N 400 V
1.11
3 AC with N
57,7 V
VDE-AR-N 4110:2018-11
VDE-AR-N 4120:2018-11
1.12
3 AC without N 100 V
1.13
3 AC with N
230 V
1.14
3 AC without N 400 V
2.00
3 AC without N
(with VG1200)
690 V
VDE-AR-N 4110:2018-11
VDE-AR-N 4120:2018-11
2.01
800 V
2.02
1000 V
1.10
3 AC with N
230 V
TOR Erzeuger Typ A, B, C, D
1.15
3 AC with N
230 V
NA/EEA-NE7 CH 2020
1.20
3 AC with N
230 V
G98(G83/2) + G99(G59/3)
1.21
3 AC without N 400 V
1.22
3 AC with N
63,5 V
1.23
3 AC without N 110 V
1.16
3 AC with N
230 V
Synergrid C10/C11
1.30
3 AC with N
230 V
SFS-EN50549-1+2:2019
1.31
3 AC without N 400 V
1.32
3 AC with N
230 V
EN50549-1 2-stage
1.33
3 AC without N 400 V
1.34
3 AC with N
230 V
NEN-EN50549-1:2019
1.36
3 AC with N
230 V
VDE 0126 VFR2019
1.40
3 AC with N
230 V
NRS097
1.41
3 AC without N 400 V
1.42
3 AC with N
230 V
AS4777,2
set ex works